S-BT Screw-in threaded studs
2.8.2 Protective bonding circuit
Fordischargingshortcircuitcurrentwhileprotectingelectricalequipmentorearth /
groundcabletraysandladders.
Single point connection:
Recommended electrical
connectors:
Max.shortcircuit
currentaccordingto
IECandUL:
Connection
conguration:
TypeAconnection:
S-BT-ERM10/15SN6
S-BT-ERW10/15SN6
S-BT-EFM10/15AN6
S-BT-EFW10/15AN6
S-BT-ERM8/15SN6
S-BT-EFM8/15AN6
I
cw
=1.20kA(IEC)
I
cw
=0.75kA(UL)
Type B connection
withHiltistandoffadapter:
S-BT-ERM10HC120
S-BT-EFM10HC120
I
cw
=1.20kA(IEC)
TypeBconnection:
S-BT-ERM10HC120
S-BT-EFW10HCAWG4/0
S-BT-EFM10HC120
S-BT-EFW10HCAWG4/0
I
cw
=14.40kA(IEC)
I
cw
=10.10kA(UL)
Note:
•Recommendedmaximalcrosssectionofconnectedcableaccording
IEC60947-7-2andIEC60947-7-1:
10mm²(8AWG)copper(testedshortcircuitcurrentI
cw
=1.20kAfor1s)
120mm²(4/0AWG)copper(testedshortcircuitcurrentI
cw
=14.40kAfor1s)
accordingUL467:
10AWGcopper(testedshortcircuitcurrentI
cw
=0.75kAfor4s)
4/0AWGcopper(testedshortcircuitcurrentI
cw
=10.10kAfor9s)
•Fasteningofthickercableisacceptable,ifthemaximumshortcircuitcurrentI
cw
andtheexposuretimeisnotexceededandtheprovisionsoncable
lugthicknesst
cl
areobserved.