21
Fitting Adjustment Values for Determining Run Length
5.1 Fitting Adjustment Values for Determining Run Length
Table 5.1 Length to Add to Each Run for Each Fitting
Fitting Pipe Size Add
Coupler
½" 1.6'
¾" 2.2'
1" 2.9'
1¼" 3.5'
1½" 4.2'
2" 3.4'
Elbow
½" 3.2'
¾" 4.4'
1" 5.7'
1¼" 6.9'
1½" 8.2'
2" 8.3'
Tee (In Line Flow)
½" 2.1'
¾" 2.9'
1" 3.7'
1¼" 4.5'
1½" 5.3'
2" 4.8'
Tee (line to branch ow)
½" 3.8'
¾" 5.3'
1" 6.8'
1¼" 8.4'
1½" 9.9'
2" 10.4'