Submittal Sheet

SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
63-2629—06 4
Fig. 2. Series 61 and 62 Modutrol IV Motor mounting dimensions in inches (mm).
Table 5. Series 61 and 62 Modutrol IV Motor Timing and Torque Ratings.
NOTE: Torque designation corresponds to torque rating at
standard timing (nominally 60 seconds for 160° and
30 seconds for 90° except for 300 lb-in. motors that
have timings of 2 or 4 minutes).
IMPORTANT
Never use motor continuously at the Breakaway
Torque rating.
Nominal Timing
a
in sec
Rated Torque in lb-in. (N•m)
b
Normal Running Torque Breakaway Torque
c
90° Stroke 160° Stroke Spring Return Non-Spring Return Spring Return Non-Spring Return
15 30 75 (8.5) 150 (17.0)
30 60 60 (6.8) 35 (4.0) 120 (13.6) 70 (7.9)
150 (17.0) 300 (34.0)
60 120 300 (34.0) 600 (68.0)
120 240
150 (17.0) 300 (34.0)
a
Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque.
b
Torque ratings for dual-ended shaft motors are the sum of the shaft torques (power-end torque plus auxiliary-end torque).
c
Breakaway torque is the maximum torque available to overcome occasional large loads such as a seized damper or valve.
M18998B
4-7/8
(124)
5-1/2
(140)
13/16
(20)
4-1/16 (103)
1/4
(7)
1-1/2 (37)
4-1/16 (103)
JUNCTION
BOX
MOTOR
AUXILARY
END
POWER
END
ADAPTER
BRACKET
2-9/16
(66)
5-3/8
(137)
6-7/16
(164)
9/16 (15)
3/4
(19)
TOP VIEW OF BRACKET TOP VIEW
4-5/8
(116)
4-1/4
(107)
2-5/16
(58)
11/16
(17)
4-7/8 (124)
5-9/16 (141)
1/4 (7)
5-13/16
(148)
1
POWER END
2
3
1-1/2 (37)
3/4
(19)
SPRING RETURN MODEL SHOWN
FOR 60 LB-IN. SPRING RETURN MODELS 8-3/4 (222).
FOR NON-SPRING RETUIRN MODELS 7-5/16 (185).
FOR 60 LB-IN. SPRING RETURN MODELS (SHOWN).
FOR NON-SPRING RETURN MODELS.
1
2
3
13/16
(20)