UDC2500 Universal Digital Controller Product Manual 51-52-25-127 April 2007 Honeywell Process Solutions Industrial Measurement and Control
Notices and Trademarks Copyright 2007 by Honeywell Revision 5 April 2007 WARRANTY/REMEDY Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective.
About This Document Abstract This document provides descriptions and procedures for the Installation, Configuration, Operation, and Troubleshooting of your UDC2500 Controller. Contacts World Wide Web The following lists Honeywell’s World Wide Web sites that will be of interest to our customers. Honeywell Organization WWW Address (URL) Corporate http://www.honeywell.com Industrial Measurement and Control http://www.honeywell.com/ps Technical tips http://content.honeywell.
Introduction Symbol Definitions The following table lists those symbols used in this document to denote certain conditions. Symbol Definition This CAUTION symbol on the equipment refers the user to the Product Manual for additional information. This symbol appears next to required information in the manual. WARNING PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.
Introduction Contents 1 INTRODUCTION ...................................................................................................1 1.1 Overview.........................................................................................................................................1 1.2 Function of Displays and Keys .......................................................................................................3 1.3 Process Instrument Explorer Software.....................................
Introduction 4 MONITORING AND OPERATING THE CONTROLLER..................................... 89 4.1 Overview.......................................................................................................................................89 4.2 Operator Interface .........................................................................................................................90 4.3 Entering a Security Code ....................................................................................
Introduction 5.5 Input 1 Calibration Procedure .....................................................................................................144 5.6 Input 2 Set Up Wiring.................................................................................................................146 5.7 Input 2 Calibration Procedure .....................................................................................................147 5.8 Restore Input Factory Calibration..................................
Introduction 10.4.1 10.4.2 Register Addresses for Read Onlys ..............................................................................192 SetPoint Program Read Only Information....................................................................192 10.5 Setpoints ..................................................................................................................................193 10.6 Using a Computer Setpoint (Overriding Controller Setpoint) ........................................
Introduction Tables Table 2-1 Condensed Specifications _____________________________________________________ 8 Table 2-2 Control Relay Contact Information _____________________________________________ 14 Table 2-3 Alarm Relay Contact Information ______________________________________________ 14 Table 2-4 Mounting Procedure_________________________________________________________ 16 Table 2-5 Permissible Wiring Bundling__________________________________________________ 18 Table 2-6 Universal Output Function
Introduction Table 4-26 Run/Monitor Functions ____________________________________________________ 123 Table 5-1 Voltage, Milliamp and Resistance Equivalents for Input 1 Range Values ______________ 137 Table 5-2 Voltage and Milliamp Equivalents for Input 2 Range Values ________________________ 139 Table 5-3 Equipment Needed _________________________________________________________ 139 Table 5-4 Set Up Wiring Procedure for Thermocouple Inputs Using an Ice Bath ________________ 140 Table 5-5 Set Up Wiring Pr
Introduction Table 10-7 Computer Setpoint Selection ________________________________________________ 194 Table 10-8 Computer Setpoint Associated Parameters _____________________________________ 195 Table 10-9 Set-up Group – Tuning ____________________________________________________ 196 Table 10-10 Set-up Group – Setpoint Ramp/Rate _________________________________________ 198 Table 10-11 Set-up Group – Accutune__________________________________________________ 201 Table 10-12 Set-up Group – Algorithm ____
Introduction Figures Figure 1-1 UDC2500 Operator Interface (all display items shown) _____________________________ 2 Figure 1-2 Screen capture of Process Instrument Explorer running on a Pocket PC _________________ 4 Figure 1-3 Depiction of infrared communications ___________________________________________ 5 Figure 2-1 Model Number Interpretation _________________________________________________ 13 Figure 2-2 Mounting Dimensions (not to scale)____________________________________________ 15 Figure 2-3 Moun
Introduction Figure 5-8 Wiring Connections for 0 to 20 mA or 4 to 20 mA Input – Input 2 ___________________ 146 Figure 5-9 Wiring Connections for 0 to 2 Volts, 0 to 5 Volts or 1 to 5 Volts Input – Input 2 ________ 147 Figure 6-1 Wiring Connections for Calibrating Current Output ______________________________ 152 Figure 6-2 Wiring Connections for Calibrating Auxiliary Output _____________________________ 154 Figure 8-1 UDC2500 Exploded View __________________________________________________ 177 Figure 10-1
Introduction 1 Introduction 1.1 Overview Function The UDC2500 is a microprocessor-based stand-alone controller. It combines a high degree of functionality and operating simplicity in a 1/4 DIN size controller. This instrument is an ideal controller for regulating temperature and other process variables in numerous heating and cooling applications, as well as in metal working, food, pharmaceuticals, semiconductor, testing and environmental work.
Introduction Mount Anywhere This instrument is intended for industrial control applications. It must be panel mounted with the wiring terminals enclosed within the panel. The instrument is environmentally hardened and, when suitably enclosed, can be mounted anywhere in plant or factory, on the wall, or even on the process machine itself. The front face is NEMA3 and IP55 rated and can be easily changed to NEMA4X and IP66 for the most severe hose-down applications.
Introduction 1.2 Function of Displays and Keys Table 1-1 shows each key on the operator interface and defines its function. Table 1-1Function of Displays and Keys Key Setup Function • Places the controller in the Configuration Set Up group select mode. Sequentially displays Set Up groups and allows the FUNCTION key to display individual functions in each Set Up group. Function • Used in conjunction with the SET UP key to select the individual functions of a selected Configuration Set Up group.
Introduction 1.3 Process Instrument Explorer Software Overview Process Instrument Explorer lets you configure your instrument on a desktop/laptop or Pocket PC. For details see Process Instrument Explorer manual #51-52-25-131. Features • Create configurations with intuitive software program running on either a Pocket PC, a Desktop or a laptop computer. · • Create/edit configurations live, just connect software to controller via comm port.
Introduction No need to get access to the back of the controller to communicate with the instrument, no need to take your screw driver to wire the communication cable, no wiring mistake possible. You can now duplicate an instrument’s configuration, upload or download a new configuration in a matter of seconds, just by pointing your Pocket PC in the direction of the instrument. It takes just a few seconds to upload a configuration from an instrument.
Introduction Pollution Degree: Pollution Degree 2: Normally non-conductive pollution with occasional conductivity caused by condensation. (Ref. IEC 664-1) EMC Classification: Group 1, Class A, ISM Equipment (EN61326, emissions), Industrial Equipment (EN61326, immunity) Method of EMC Assessment: Technical File (TF) Declaration of Conformity: 51453655 Deviation from the installation conditions specified in this manual, and the special conditions for CE conformity in Subsection 2.
Installation 2 Installation 2.1 Overview Introduction Installation of the UDC2500 consists of mounting and wiring the controller according to the instructions given in this section. Read the pre-installation information, check the model number interpretation (Subsection 2.3), and become familiar with your model selections, then proceed with installation. What’s in this section? The following topics are covered in this section. TOPIC 4/07 See Page 2.1 Overview 7 2.2 Condensed Specifications 8 2.
Installation Pre-installation Information If the controller has not been removed from its shipping carton, inspect the carton for damage then remove the controller. • Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier. • Make sure a bag containing mounting hardware is included in the carton with the controller. • Check that the model number shown on the inside of the case agrees with what you have ordered. 2.
Installation Controller Output Types Alarm Outputs (Optional) Isolation (Functional) Specifications Electromechanical Relays (One or Two) SPDT contacts. Both Normally Open and Normally Closed contacts are brought out to the rear terminals. Internally socketed. Resistive Load: 5 amps @ 120 Vac or 240 Vac or 30 Vdc Inductive Load (cosϕ = 0.4): 3 amps @ 130 Vac or 250 Vac Inductive Load (L/R = 7 msec): 3.5 amps @ 30 Vdc Motor: 1/6 H.P. Dual Electromechanical Relays Two SPST contacts.
Installation RS422/485 Modbus RTU Communications Interface (Optional) Specifications Baud Rate: 4800, 9600,19,200 or 38,400 baud selectable Data Format: Floating point or integer Length of Link: 2000 ft (600 m) max. with Belden 9271 Twinax Cable and 120 ohm termination resistors 4000 ft. (1200 m) max. with Belden 8227 Twinax Cable and 100 ohm termination resistors Link Characteristics: Two-wire, multi-drop Modbus RTU protocol, 15 drops maximum or up to 31 drops for shorter link length.
Installation Environmental and Operating Conditions Parameter Reference Rated Operative Limits Transportation and Storage Ambient Temperature 25 ± 3 °C 77 ± 5 °F 15 to 55 °C 58 to 131 °F 0 to 55 °C 32 to 131 °F –40 to 66 °C –40 to 151 °F Relative Humidity 10 to 55* 10 to 90* 5 to 90* 5 to 95* Vibration Frequency (Hz) Acceleration (g) 0 0 0 to 70 0.4 0 to 200 0.6 0 to 200 0.
Installation 2.3 Model Number Interpretation Introduction Write your controller’s model number in the spaces provided below and circle the corresponding items in each table. This information will also be useful when you wire your controller. Instructions Select the desired key number. The arrow to the right marks the selection available. Make the desired selections from Tables I through VI using the column below the proper arrow. A dot ( ) denotes availability.
Installation TABLE V - Product Manuals Product Information on CD - English English (Hard Copy) Manual French (Hard Copy) Manual German (Hard Copy) Manual Italian (Hard Copy) Manual Spanish (Hard Copy) Manual None Certificate of Conformance (F3391) Manuals Certificate (51-52-25-127) (51-52-25-127-FR) (51-52-25-127-DE) (51-52-25-127-IT) (51-52-25-127-SP) 0_ E_ F_ G_ I_ S_ _0 _C TABLE VI No Selection None 0 RESTRICTIONS Available Only With Not Available With Selection Table Selection Table E_ I A_ a I
Installation 2.4 Control and Alarm Relay Contact Information Control Relays ATTENTION Control relays operate in the standard control mode (that is, energized when output state is on). Table 2-2 Control Relay Contact Information Unit Power Control Relay Wiring Control Relay Contact Off N.O. Open N.C. Closed N.O. Open Off Closed On Closed Off Open On On N.C.
Installation 2.5 Mounting Physical Considerations The controller can be mounted on either a vertical or tilted panel using the mounting kit supplied. Adequate access space must be available at the back of the panel for installation and servicing activities. • Overall dimensions and panel cutout requirements for mounting the controller are shown in Figure 2-2. • The controller’s mounting enclosure must be grounded according to CSA standard C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.
Installation Mounting Method Before mounting the controller, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration. Mounting clips Attach screws and washers here for water protection Figure 2-3 Mounting Methods Mounting Procedure Table 2-4 Mounting Procedure Step Action 1 Mark and cut out the controller hole in the panel according to the dimension information in Figure 2-2.
Installation 2.6 Wiring 2.6.1 Electrical Considerations Line voltage wiring This controller is considered “rack and panel mounted equipment” per EN61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requires the user to provide adequate protection against a shock hazard. The user shall install this controller in an enclosure that limits OPERATOR access to the rear terminals.
Installation Digital equipment is especially sensitive to the effects of electrical noise. Your controller has built-in circuits to reduce the effect of electrical noise from various sources. If there is a need to further reduce these effects: • Separate External Wiring—Separate connecting wires into bundles (See Permissible Wiring Bundling - Table 2-5) and route the individual bundles through separate conduit metal trays.
Installation 2.7 Wiring Diagrams Identify Your Wiring Requirements To determine the appropriate diagrams for wiring your controller, refer to the model number interpretation in this section. The model number of the controller is on the outside of the case. Universal Output Functionality and Restrictions Instruments with multiple outputs can be configured to perform a variety of output types and alarms.
Installation Table 2-6 Universal Output Functionality and Restrictions Output Algorithm Type Output 1/2 Option Function of Output 1/2 Time Simplex Single Relay Current Output Dual Relay Output 1 INU Output 1 Time Duplex or TPSC Single Relay Current Output Dual Relay Output 1 INU Outputs 1 and 2 Output 2 Output 2 Alarm 2 Alarm 1 Output 1 Alarm 1 Not Needed Not Needed Not Needed Current Simplex Single Relay Current Output Dual Relay INU Output 1 INU Alarm 2 Alarm 2 Alarm 2 Alarm 1 Alarm 1 Ala
Installation selections, the Output 1 (HEAT) and Output 2 (COOL) signals will be present both on the Auxiliary Output and on the two relays normally used for Time Duplex. Wiring the Controller Using the information contained in the model number, select the appropriate wiring diagrams from the composite wiring diagram below. Refer to the individual diagrams listed to wire the controller according to your requirements.
Installation 1 3 AC/DC Line Voltage 2 Earth Ground 10 19 L1 11 20 L2/N 12 21 4 13 22 5 14 23 6 15 24 7 16 25 8 17 26 9 18 Hot Neutral 27 1 PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed, shall be in accordance with National and local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary 2 bonding of the controller enclosure to local ground using a No.
Installation Input #1 Thermocouple Millivolt or Volts except 0-10 Volts RTD Use Thermocouple extension wire only 25 R 25 R 26 + 26 + 27 – 27 – source 25 R 3 0-10 Volts 0–10 Volt source + 1 – mV or Volt source Milliamps 100K 1 2 100K 3 25 R 26 + 27 – + 1 250 Ω Power + – Supply 26 + – 27 – Thermocouple Differential 25 R – Xmitter + 26 + 27 – Use Thermocouple extension wire only + – – + 4 2 25 R 26 + 27 – 1 The 250 ohm resistor for milliamp inputs or the voltage divider
Installation Input #2 Milliamps Input Volts Input mV or Volt Voltage source source 1 22 mA+ – 22 mA+ Xmitter + + 23 V+ 23 V+ Power – 1 + 24 – – 24 – Supply The dropping resistor for milliamp inputs is internal to the controller. Figure 2-7 Input 2 Connections Time Simplex 19 L1 Output Relay#1 N.C. 20 N.O. 21 L2/N 4 Load Supply Power Relay Load 2 To terminal 4 or 6 5 Relay Load 2 To terminal 7 or 9 Alarm N.O.
Installation Time Simplex Dummy Resistor 1 19 L1 Output Relay#1 20 N.O. 21 L2/N 4 Load Supply Power Relay Load 3 To terminal 4 or 6 5 Relay Load 3 To terminal 7 or 9 N.C. Alarm Relay#2 N.O. 8 2 22 23 24 6 7 Load Supply Power Load Supply Power Relay Load N.C. Alarm Relay#1 N.O. 9 25 26 27 Time Duplex 1 19 L1 1 Dummy Resistor Relay Load 5 Load Supply Power 7 Relay Load To terminal 7 or 9 8 9 Relay Load 21 Output Relay#2 N.O. 22 Load Supply Power 2 23 24 6 2 20 N.O.
Installation Time Simplex Customer Supplied Electromechanical relay 19 L1 L2/N 4 Load Supply Power Relay Load Load Supply Power 21 Relay Load N.C. Alarm Relay#1 N.O.
Installation Time Duplex with a Dual Relay Board Out Relay#2 L1 Out Relay#1 4 N.O. Relay Load 2 Load Supply Power To terminal 4 or 6 N.O. To terminal 7 or 9 1 23 24 6 7 Relay Load 2 5 22 Alarm Relay#2 Supply Power Heat Relay Load 21 N.C. Load 20 L2/N Load Supply Power Cool Relay Load 19 N.O. N.C. 25 Alarm N.O. Relay#1 8 9 26 27 Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or 30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.
Installation Open (CW) Motor Power Supply 20 Close (CCW) L2/N 2 5 6 L1/Hot 21 Control Relay #1 1 Control Relay #2 1 Alarm #2 is not available with this configuration. 2 Electromechanical Relays are rated at 5 amps at 120 Vac or 240 Vac or 24 Vdc. Solid State Relays are rated at 1 Amp at 25°C and derated linearly to 0.5 Amps at 55°C. Customer should size fuses accordingly. Use Fast Blo fuses only.
Installation COMMUNICATION MASTER D+ (B) SHLD 2 1 16 SHLD SHLD 17 D+ (B) D+ 18 D– (A) D– D– (A) 120 OHMS TO OTHER COMMUNICATION CONTROLLERS D– Connect shield to ground at one end only. D+ 120 OHMS ON LAST LEG 1 Do not run the communications lines in the same conduit as AC power. 2 Use shielded twisted pair cables (Belden 9271 Twinax or equivalent).
Installation Table 2-7 Terminals for connecting a UDC to a MDI Compliant Hub or Switch UDC Terminal UDC Signal Name RJ45 Socket Pin # Switch Signal Name Position 14 Shield Shield Shield Position 15 RXD- 6 TXD- Position 16 RXD+ 3 TXD+ Position 17 TXD- 2 RXD- Position 18 TXD+ 1 RXD+ Table 2-8 shows how to connect a UDC directly to a PC utilizing a straight-through cable (wiring the UDC cable this way makes the necessary cross-over connections) Table 2-8 Terminals for connecting a UDC
Installation 2 Wire Transmitter Configure: A2S1TY = NONE A2S2TY = NONE 1 _ + 5+ 26 + 27 - 250 Ω 6OUTPUT 3 INPUT 1 1 If necessary, install a zener diode here to reduce voltage at the transmitter. A 1N4733 will reduce the voltage at the transmitter to approximately 25 Vdc.
Configuration 3 Configuration 3.1 Overview Introduction Configuration is a dedicated operation where you use straightforward keystroke sequences to select and establish (configure) pertinent control data best suited for your application. To assist you in the configuration process, there are prompts that appear in the upper and lower displays.
Configuration 3.2 Configuration Prompt Hierarchy Table 3-2 Configuration Prompt Hierarchy Set Up Group TUNING Function Prompts PB or GAIN RATE T I MIN or I RPM MANRST PB 2 or GAIN 2 RATE2T CYC2T2 or CT2 X3 SECUR LOCK AUTOMA RN HLD SP SL SPRAMP TI MIN FINLSP SPRATE EUHRUP ENDSEG RPUNIT RECYCL SOKDEV PG END SGx RP* SGxSP* SGx TI* * x = 1 to 12.
Configuration 3.3 Configuration Procedure Introduction Each of the Set Up groups and their functions are pre-configured at the factory. The factory settings are shown in Table 3-4 through Table 3-15 that follow this procedure. If you want to change any of these selections or values, follow the procedure in Table 3-3. This procedure tells you the keys to press to get to any Set Up group and any associated Function parameter prompt.
Configuration 3.4 Tuning Set Up Group Introduction Tuning consists of establishing the appropriate values for the tuning constants you are using so that your controller responds correctly to changes in process variable and setpoint. You can start with predetermined values but you will have to watch the system to see how to modify them. The Accutune feature automatically selects Gain, Rate, and Reset on demand.
Configuration Function Prompt Lower Display English Numeric Code Selection or Range of Setting Upper Display English Parameter Definition Numeric Code Also defined as "HEAT" Rate on Duplex models for variations of Heat/Cool applications. I MIN or I RPM 103 0.02 to 50.00 I MIN = Reset in Minutes per Repeat 0.02 to 50.00 I RPM = Reset in Repeats per Minute Integral Time (or Reset) adjusts the controller's output in accordance with both the size of the deviation (SP–PV) and the time that it lasts.
Configuration Function Prompt Lower Display English Numeric Code I2 MIN or I2 RPM 107 CYC T1 or CT1 X3 108 Selection or Range of Setting Upper Display English Parameter Definition Numeric Code These are the same as above except that they apply to Duplex models for the "COOL" zone of Heat/Cool applications or for the second set of PID constants. 0.02 to 50.00 0.02 to 50.00 CYCLE TIME (HEAT) determines the length of one time proportional output relay cycle.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code read/write. AUTOMA CAL 1 CALIBRATION—All groups are available for read/write except for the Calibration and Keyboard Lockout groups. CONF 2 + CONFIGURATION—Tuning, SP Ramp, and Accutune groups are read/write. All other groups are read only. Calibration and Keyboard Lockout groups are not available.
Configuration 3.5 SP Ramp Set Up Group Introduction Set Point Ramp, Set Point Programs and Set Point Rates can be configured in this group. A single Setpoint Ramp [SP RAMP] can be configured to occur between the current local setpoint and a final local setpoint over a time interval of from 1 to 255 minutes. A Set Point Rate [SPRATE] lets you configure a specific rate of change for any local setpoint change. A single Set Point Program [SP PROG] with up to 12 segments can be configured.
Configuration Function Prompt Lower Display English FINLSP Selection or Range of Setting Upper Display Numeri c Code 203 English Parameter Definition Numeric Code Enter a value within the setpoint limits SETPOINT RAMP FINAL SETPOINT— Enter the value desired for the final setpoint. The controller will operate at the setpoint set here when ramp is ended. ATTENTION If the ramp is on HOLD, the held setpoint can be changed by the ▲ and ▼ keys.
Configuration Function Prompt Lower Display English EUHRDN Selection or Range of Setting Upper Display Numeri c Code 206 English Parameter Definition Numeric Code 0 to 9999 in Engineering units per hour RATE DOWN—Rate down value. When making a setpoint change, this is the rate at which the controller will change from the original setpoint down to the new one. The ramping (current) setpoint can be viewed as SPn in the lower display. Entering a 0 will imply an immediate change in Setpoint (i.e.
Configuration Function Prompt Lower Display English Numeri c Code Selection or Range of Setting Upper Display English Parameter Definition Numeric Code STATE 214 DIS HOLD 0 1 Program State at Program End ToBEGN 215 DIS KEY (Keyboard) 0 1 Reset/Rerun SP Program PVSTRT 216 DIS ENAB 0 1 DISABLE—LSP1 is used as the initial ramp setpoint. ENABLE—Current PV value is used as the initial ramp setpoint.
Configuration 3.6 Accutune Set Up Group Introduction Accutune III automatically calculates GAIN, RATE, and RESET TIME (PID) tuning constants for your control loop. When initiated on demand, the Accutune algorithm measures a process step response and automatically generates the PID tuning constants needed for no overshoot on your process.
Configuration Function Prompts Table 3-6 ATUNE Group (Numeric Code 300) Function Prompts Function Prompt Lower Display English FUZZY TUNE Selection or Range of Setting Upper Display Numeric Code English 44 Numeric Code 301 FUZZY OVERSHOOT SUPPRESSION— Can be enabled or disabled independently of whether Demand Tuning or SP Tuning is enabled or disabled. DIS 0 DISABLE—Disables Fuzzy Overshoot Suppression.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Numeric Code DIS AT ERR (Read Only) 4/07 Parameter Definition DISABLE – The current SetPoint is used to derive a single set of blended tuning parameters. This tuning is performed over the range of the output limits similar to Simplex Tuning. The Tuning Parameters derived are placed into both the HEAT and COOL tune sets (PID 1 and PID 2).
Configuration 3.7 Algorithm Set Up Group Introduction This data deals with various algorithms in the controller and Timer functions. The Timer section allows you to configure a time-out period and to select the timer start by either the keyboard (RUN/HOLD key) or Alarm 2. An optional digital input can also be configured to the start the timer. The timer display is selectable as either “time remaining” (see TREM) or “elapsed time” (see ET). Alarm 1 is activated at the end of the time-out period.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code DUPLEX ON/OFF is an extension of this algorithm when the output is configured for Duplex. It allows the operation of a second ON/OFF output. There is a deadband between the operating ranges of the two inputs and an adjustable overlap (hysteresis) of the on and off states of each output. Both Deadband and Hysteresis are separately adjustable.
Configuration Function Prompt Lower Display English Numeric Code Selection or Range of Setting Upper Display English PDMR Parameter Definition Numeric Code 3 PD WITH MANUAL RESET is used whenever integral action is not wanted for automatic control. The equation is computed with no integral contribution. The MANUAL RESET, which is operator adjustable, is then added to the present output to form the controller output. Switching between manual and automatic mode will be bumpless.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code The actual slidewire position is then shown on the lower display as POS. This value is used for display only. It is NOT used in the Three Position Step algorithm. To configure this option, set Input 2 actuation to SLIDEW. Calibrate the slidewire.
Configuration Function Prompt Lower Display English L DISP Selection or Range of Setting Upper Display Numeric Code 405 English TREM ET Parameter Definition Numeric Code 0 1 L DISP allows you to select whether time remaining (TI REM) or elapsed time (E TIME) is displayed for the timer option. The time is shown on the lower display in HH:MM format along with a rotating “clock” character. • If the “clock” rotation is clockwise, elapsed time is indicated.
Configuration 3.8 Output Set Up Group Introduction This group deals with various output types in the controller, the Digital Output Status and the Current Output operation. ATTENTION The Tuning Group is automatically configured to have two PID sets when a Duplex Control Algorithm is selected.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code CUR 2 RLYD 3 CURD 4 CURRENT SIMPLEX—Type of output using one 4 mA to 20 mA signal that can be fed into a positive or negative grounded load of 0 to 1000 ohms. This signal can easily be configured for 4-20 mA or 0-20 mA operation via the CRANGE configuration, below.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English 50 Parameter Definition Numeric Code CURRENT DUPLEX RANGE (SPLIT)—This setting should be used for Relay/Current and Current/Relay Duplex Outputs. It can also be used for Current Duplex when an Auxiliary Output board is present. This enables the normal control current output to provide heat control and the auxiliary current output to provide cool control.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code RELAY CYCLE TIME INCREMENT selection is used only for Time Simplex and Duplex output configurations. This configuration sets the increment size of the relay cycle times in the Tuning and Tuning 2 Set Up groups. RLY TYP MECH 0 ELECTROMECHANICAL RELAY—Cycle time in one-second increments. SS 1 SOLID STATE RELAY—Cycle time in 1/3 second increments.
Configuration 3.9 Input 1 Set Up Group Introduction This data deals with various parameters required to configure Input 1. Function Prompts Table 3-9 INPUT 1 Group (Numeric Code 600) Function Prompts Function Prompt Lower Display English IN1TYP Numeric Code Selection or Range of Setting Upper Display English Numeric Code 601 INPUT 1 ACTUATION TYPE – This selection determines what actuation you are going to use for Input 1.
Configuration Function Prompt Lower Display English XMITR1 IN1 HI Numeric Code 602 603 Selection or Range of Setting Upper Display English B EH EL JH JM JL KH KM KL NNMH NNML NICH NICL R S TH TL WH WL 100H 100L 200 500 RADH RADI LIN SrT −999 to 9999 floating in engineering units Parameter Definition Numeric Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 TRANSMITTER CHARACTERIZATION— This selection lets you instruct the controller to characterize a linear input to repre
Configuration Function Prompt Lower Display English IN1 LO Selection or Range of Setting Upper Display Numeric Code 604 English Parameter Definition Numeric Code INPUT 1 LOW RANGE VALUE in engineering units is displayed for all inputs but can only be configured for linear or square root transmitter characterization. Scale the #1 input signal to the display value you want for 0 %. See example above.
Configuration Function Prompt Lower Display English Numeric Code Selection or Range of Setting Upper Display English DOWN Parameter Definition Numeric Code 2 DOWNSCALE BURNOUT will force the Input 1 signal to the lower range value when the sensor fails. Diagnostic message IN1 FAIL intermittently flashed on the lower display. The controller remains in Automatic control mode and adjusts the controller output signal in response to the lower range Input 1 signal developed by the Burnout circuitry.
Configuration 3.10 Input 2 Set Up Group Introduction This data deals with various parameters required to configure Input 2. Function Prompts Table 3-10 INPUT2 Group (Numeric Code 700) Function Prompts Function Prompt Lower Display English IN2TYP XMITR2 4/07 Selection or Range of Setting Upper Display Numeric Code English Numeric Code 701 702 Parameter Definition INPUT 2 ACTUATION TYPE – This selection determines what actuation you are going to use for Input 2.
Configuration Function Prompt Lower Display English IN2 HI Numeric Code 703 Selection or Range of Setting Upper Display English −999 to 9999 floating in engineering units Parameter Definition Numeric Code INPUT 2 HIGH RANGE VALUE in engineering units is displayed for all inputs but can only be configured for linear or square root transmitter characterization. Scale the #2 input signal to the display value you want for 100 %.
Configuration 3.11 Control Set Up Group Introduction The functions listed in this group deal with how the controller will control the process including: Number of Tuning Parameter Sets, Setpoint Source, Tracking, Power-up Recall, Setpoint Limits, Output Direction and Limits, Deadband, and Hysteresis.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English 2 PR Parameter Definition Numeric Code 2 TWO SETS PV AUTOMATIC SWITCHOVER—When the process variable is GREATER than the value set at prompt SW VALUE (Switchover Value), the controller will use Gain, Rate, Reset, and Cycle Time. The active PID SET can be read in the lower display.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English TWO RSPSRC Numeric Code 1 TWO LOCAL SETPOINTS—This selection lets you switch between two local setpoints using the SETPOINT SELECT key. REMOTE SETPOINT SOURCE— This selection lets you switch between the local and remote setpoints using the SETPOINT SELECT key. 804 NONE INP2 SP TRK Parameter Definition 0 1 NONE—No remote setpoint. INPUT 2—Remote Setpoint is Input 2.
Configuration Function Prompt Lower Display English PWROUT Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code ARSP 2 AUTOMATIC MODE, LAST RSP—At power-up, the controller will use automatic mode with the last remote setpoint used before power down displayed. AMSP 3 LAST MODE/LAST SETPOINT used before power down. AMLS 4 LAST MODE/LAST LOCAL SETPOINT on power down.
Configuration Function Prompt Lower Display English OUT Hi OUT Lo D BAND HYST Selection or Range of Setting Upper Display Numeric Code English Numeric Code HIGH OUTPUT LIMIT—This is the highest value of output beyond which you do not want the controller automatic output to exceed. 811 0 % to 100 % For relay output types. –5 % to 105 % For current output types. LOW OUTPUT LIMIT—This is the lowest value of output below which you do not want the controller automatic output to exceed.
Configuration Function Prompt Lower Display English FSMODE PBorGN MINRPM Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code 817 FAILSAFE MODE No L 0 NON LATCHING—Controller stays in last mode that was being used (automatic or manual); output goes to failsafe value. (NOTE 1, NOTE 2) LACH 1 LATCHING—Controller goes to manual mode; output goes to failsafe value.
Configuration 3.12 Options Group Introduction The Options group lets you configure the remote mode switch (Digital Inputs) to a specific contact closure response, or configure the Auxiliary Output to be a specific selection with desired scaling.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English DEV Parameter Definition Numeric Code 4 DEVIATION (PROCESS VARIABLE MINUS SETPOINT)—Represents –100 % to +100 % of the selected PV span in engineering units. Zero deviation will produce a center scale (12 mA or 50 %) output. A negative deviation equal in magnitude to the Auxiliary Output High Scaling Factor will produce a low end output (4 mA or 0 %) output.
Configuration Function Prompt Lower Display English 100 PCT Selection or Range of Setting Upper Display Numeric Code 903 English Parameter Definition Numeric Code Value in Engineering Units AUXILIARY OUTPUT HIGH SCALING FACTOR— This is a value in engineering units used to represent all AUX OUT parameters except Output. For Output, this is a value in percent and can be any value between –5 % and +105 %. However, keep in mind that relay output types can only be scaled 0 % to 100 %.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English HOLD Parameter Definition Numeric Code 5 TO HOLD—Contact closure suspends Setpoint Program or Setpoint Ramp. When contact reopens, the controller starts from the Hold point of the Ramp/Program unless the Ramp/Program was not previously started via the RUN/HOLD key. This selection applies to either loop. PID2 6 TO PID2—Contact closure selects PID Set 2.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code TIMR 12 TIMER—Contact closure starts timer, if enabled. Reopening the switch has no effect. TUNE 13 INITIATE LIMIT CYCLE TUNING—Contact closure starts the slow tuning process. The lower display shows DoSLOW. Opening the contact has no effect. INIT 14 SETPOINT INITIALIZATION—Contact closure forces the setpoint to the current PV value.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code automatically restart at the initial Setpoint value. If power to the unit is lost while while a SP Ramp or Program was running, then if the contact is closed at power up, the unit will automatically restart the SP Ramp or Program at the captured Setpoint value.
Configuration 3.13 Communications Group Introduction The Communications group lets you configure the controller to be connected to a host computer via Modbus® or Ethernet TCP/IP protocol. Two parameters in this Group, Communications Station Address and TX Delay, are also used for IR communications. No other parameters affect IR communications. Introduction A controller with a communications option looks for messages from the host computer.
Configuration Function Prompt Lower Display English Numeric Code TX_DLY 1005 WS_FLT 1006 Selection or Range of Setting Upper Display English Parameter Definition Numeric Code 1 to 500 milliseconds TX DELAY—Configurable response-delay timer allows you to force the UDC to delay its response for a time period of from 1 to 500 milliseconds compatible with the host system hardware/software. This parameter is also used for the IR communications link.
Configuration Function Prompt Lower Display English Numeric Code Selection or Range of Setting Upper Display English AUTO SHD_SP Parameter Definition Numeric Code 3 TO AUTO—AUTOMATIC MODE, LAST SP—The controller will return to the automatic mode and the last setpoint used before shed. SHED SETPOINT RECALL 1010 Note: If SHEDENAB=DISABLE, this prompt will not be configurable. LSP 0 TO LSP—Controller will use last local or remote setpoint used.
Configuration 3.14 Alarms Set Up Group Introduction An alarm is an indication that an event that you have configured (for example—Process Variable) has exceeded one or more alarm limits. There are two alarms available. Each alarm has two setpoints. You can configure each of these two setpoints to alarm on various controller parameters. There are two alarm output selections, High and Low. You can configure each setpoint to alarm either High or Low. These are called single alarms.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English DE 2 TC W TC F Parameter Definition Numeric Code 16 17 18 DEVIATION FROM LSP 2 (NOTE 3) THERMOCOUPLE WARNING (NOTE 5) THERMOCOUPLE FAILING (NOTE 6) ATTENTION NOTE 1. When the controller is configured for Three Position Step Control, alarms set for Output will not function. NOTE 2. Alarm 1 is not available if the Timer is enabled because Alarm 1 is dedicated to Timer output. NOTE 3.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code NOTE 5. Thermocouple Warning means that the instrument has detected that the Thermocouple Input is starting to fail. Not valid for other input types. NOTE 6. Thermocouple Failing means that the instrument has detected that the Thermocouple Input is in imminent danger of failing. Not valid for other input types. NOTE 7.
Configuration Function Prompt Lower Display English A1S1EV Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code 1103 If Setpoint Programming is enabled and if the Alarm Type is configured for Event On/Off: ALARM 1 SEGMENT EVENT 1—Select whether you want the alarm type chosen in prompt A1S1TYPE to alarm the beginning or end of a segment in setpoint Ramp/Soak programming.
Configuration Function Prompt Lower Display English Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code A2S1HL 1109 HIGH LOW 0 1 ALARM 2 SETPOINT 1 STATE—Same as A1S1HL. A2S1EV 1109 BEGIN END 0 1 ALARM 2 SEGMENT EVENT 1—Same as A1S1EV. A2S2TY 1110 ALARM 2 SETPOINT 2 TYPE—Select what you want Setpoint 2 of Alarm 2 to represent. The selections are the same as A1S1TYPE. ATTENTION Not applicable with Relay Duplex unless using Dual Relay PWA.
Configuration Function Prompt Lower Display English ALARM1 Selection or Range of Setting Upper Display Numeric Code English Parameter Definition Numeric Code 1114 LATCHING ALARM OUTPUT 1—Alarm output 1 can be configured to be Latching or Non-latching. NO LAT LATCH 0 1 NO LAT—Non-latching LATCH—Latching ATTENTION When configured for latching, the alarm will stay active after the alarm condition ends until the RUN/HOLD key is pressed.
Configuration 3.15 Display Set Up Group Introduction This group includes selections for Decimal place, Units of temperature, Language and Power frequency. Function Prompts Table 3-16 DISPLY Group (Numeric Code 1200) Function Prompts Function Prompt Lower Display English DECMAL Selection or Range of Setting Upper Display Numeric Code 1201 English Parameter Definition Numeric Code DECIMAL POINT LOCATION—This selection determines where the decimal point appears in the display.
Configuration Function Prompt Lower Display English FREQ Selection or Range of Setting Upper Display Numeric Code English Numeric Code 1203 60 50 Parameter Definition 0 1 POWER LINE FREQUENCY—Select whether your controller is operating at 50 or 60 Hertz. ATTENTION For controllers powered by +24 Vdc, this configuration should be set to the AC line frequency used to produce the +24 Vdc supply. Incorrect setting of this parameter may cause normal mode noise problems in the input readings.
Configuration 3.16 P.I.E. Tool Ethernet and Email Configuration Screens Introduction These screens only appear in instruments that have Ethernet Communications. Ethernet and Email parameters can only be configured via the Process Instrument Explorer (P.I.E. Tool®). The figures in this section show screen-shots of the Configuration Screens from the PC version of the P.I.E. Tool®. Pocket PC Configuration Screens are generally similar in format but smaller.
Configuration WARNING After you change the IP Address, you will no longer be able to communicate with the instrument via Ethernet until you change the P.I.E. Tool’s IP Address setting in the PC COMM SETUP section to match the setting that is now in your controller. See Section 4.23 – Configuring your Ethernet Connection for more information. Email Configuration Screen This controller may be configured to support sending an Email when an alarm occurs.
Configuration The content of the Emails sent by this controller contains the Alarm that triggered the Email, its settings and the current value (if applicable) of the monitored variable. For example, the content of an Email triggered by Alarm 1 Setpoint 1 that is configured to monitor Input 1 would look something like this: Name: Alarm 1 SP1, Type: INPUT1, Event: HIGH/END, Value = 500.00, Actual = 712.
Configuration 3.17 Configuration Record Sheet Enter the value or selection for each prompt on this sheet so you will have a record of how your controller was configured.
Configuration Group Prompt Function Prompt Value or Selection Factory Setting Group Prompt CONTRL PIDSET SW VAL LSP’S RSPSRC SP TRK PWR UP PWROUT SP Hi SP Lo ACTION OUT Hi OUT Lo D BAND HYST FAILSF FSMODE PBorGN MINRPM _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ _______ ONE 0.00 ONE NONE NONE AUTO FSAF 2400 0 REV 100 0 2.0 0.5 0.
Monitoring and Operating the Controller 4 Monitoring and Operating the Controller 4.1 Overview Introduction This section gives you all the information necessary to help you monitor and operate your controller including an Operator Interface overview, how to lockout changes to the controller, entering a security code, and monitoring the displays. What's in this section? The following topics are covered in this section. TOPIC 4.1 Overview 4/07 See Page 89 4.2 Operator Interface 90 4.
Monitoring and Operating the Controller 4.2 Operator Interface Introduction Figure 4-1 is a view of the Operator Interface. Figure 4-1 Operator Interface 4.3 Entering a Security Code Introduction The level of keyboard lockout may be changed in the Set Up mode. However, knowledge of a security code number (0 to 9999) may be required to change from one level of lockout to another.
Monitoring and Operating the Controller Table 4-1 Procedure to Enter a Security Code Step Operation Press 1 Enter Set Up Mode Setup Select any Set Up Group Function 2 Upper Display = SET UP Lower Display = TUNING Upper Display = 0 Lower Display = SECUR Security Code Entry 3 Result To enter a four digit number in the upper display (0001 to 9999) or This will be your security code. 4.
Monitoring and Operating the Controller Individual key lockout There are three keys that can be disabled to prevent unauthorized changes to the parameters associated with these keys. First set the “Lock” prompt to NONE. These keys are: Run Hold M-A Reset SP Select Key - you can disable the Run/Hold key for Set Point Programming at configuration Set Up group prompt “Tuning,” function prompt “RN HLD.
Monitoring and Operating the Controller 4.5 Monitoring Your Controller 4.5.
Monitoring and Operating the Controller 4.5.2 Viewing the operating parameters Press the LOWER DISPLAY key to scroll through the operating parameters listed in Table 4-3. The lower display will show only those parameters and their values that apply to your specific model. Table 4-3 Lower Display Key Parameter Prompts Lower Display Description OT XX.X OUTPUT—Output value is percent; for Three Position Step control, this is an estimated motor position and shown with no decimal place.
Monitoring and Operating the Controller 4.5.3 Diagnostic Messages The UDC2500 performs background tests to verify data and memory integrity. If there is a malfunction, a diagnostic message will be shown on the lower display. In the case of more than one simultaneous malfunction, only the highest priority diagnostic message will be displayed. Table 4-4 shows the error messages in order by priority.
Monitoring and Operating the Controller IN 2 IN 1 Ratio Bias Ratio Bias PV Source RSP Source PV Remote SP SP Source SP CONTROL ALGORITHM Local SP CSP SP 2SP OUTPUT To Final Control Element XXXX Figure 4-2 Functional Overview Block Diagram of the UDC2500 Controller 96 UDC2500 Universal Digital Controller Product Manual 4/07
Monitoring and Operating the Controller 4.6 Single Display Functionality Introduction This means that the displayed value of PV, Setpoint, Setpoint2, Remote Setpoint, Input 2, Output, Bias, Aux Out, and Deviation will appear on the top display and a prompt identifying the value will appear on the bottom display. Access the Values Pressing the LOWER DISPLAY key will cycle through all applicable values (configuration dependent).
Monitoring and Operating the Controller Single Display Parameters Table 4-5 Single Display Parameters Lower Display Prompt Upper Display Value Comments (blank) Process Variable Default selection PV Process Variable Default selection SP Local Setpoint #1 Default selection 2SP Local Setpoint #2 Default selection RSP Remote Setpoint Default selection OUT Output DEV Deviation 2IN Input #2 AUX Aux Output value BIA PD+MR bias value PIDS x Process Variable Active PID set RP xxxM Pr
Monitoring and Operating the Controller 4.7 Start Up Procedure for Operation Table 4-6 Procedure for Starting Up the Controller Single Display Step 1 Dual Display Step Operation 1 Configure controller 2 Select Manual Mode 3 Press Setup M-A Reset Adjust the Output Result Make sure the controller has been configured properly and that all the values and selections have been recorded on the Configuration Record Sheet. See steps 4 & 5. N/A for Single Display Model Until “M” indicator is ON.
Monitoring and Operating the Controller 4.8 Control Modes ATTENTION After changing a Local Setpoint value, if no other key is pressed, it then takes a minimum of thirty (30) seconds elapsed time before the new value is stored in non-volatile memory. If controller power is removed before this time, the new setpoint value is lost and the previous setpoint value is used at power-up. If, after changing the LSP value, another key is pressed, then the value is stored immediately. 4.8.
Monitoring and Operating the Controller 4.8.2 What happens when you change modes Table 4-8 Changing Control Modes (Dual Display Only) Control Mode Definition Manual to Automatic Local Setpoint The Local Setpoint is usually the value previously stored as the Local Setpoint. PV tracking is a configurable feature which modifies this. For this configuration, when the controller is in manual mode, the local setpoint value tracks the process variable value continuously.
Monitoring and Operating the Controller Switching between setpoints You can switch Local and Remote setpoints or between two Local setpoints when configured. ATTENTION The REMOTE SETPOINT value cannot be changed at the keyboard.
Monitoring and Operating the Controller Viewing Times The times are viewed on the lower display as follows: TIME REMAINING will show as a decreasing Hrs:Min value (HH:MM) or Min:Sec value (MM:SS) plus a counterclockwise rotating clock face. ELAPSED TIME will show as an increasing Hrs:Min value(HH:MM) or Min:Sec value (MM:SS) plus a clockwise rotating clock face. Operation When the Timer is enabled (RUN/HOLD key or ALARM 2), it has exclusive control of Alarm 1 relay.
Monitoring and Operating the Controller 4.11 Accutune III Introduction Accutune III (TUNE) may be used for self-regulating and single integrating processes. This autotuning method is initiated on-demand, typically at initial start-up. There are no other requirements necessary, such as prior knowledge to the process dynamics or initial or post tune process line-out to setpoint or manual output.
Monitoring and Operating the Controller At the end of the tuning process, the controller immediately calculates the tuning constants and enters them into the Tuning group, and begins PID control with the correct tuning parameters. This works with any process, including integrating type processes, and allows retuning at a fixed setpoint. 4.11.1 Tune for Simplex Outputs After “TUNE” has been enabled, you can start Accutune as shown in Table 4-11.
Monitoring and Operating the Controller Configuration Check for Duplex See Subsection 3.6 - Accutune Set Up Group for details. Make sure: • TUNE has been enabled • DUPLEX has been configured to Manual, Automatic or Disabled 4.11.3 Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool) Used when DUPLEX has been configured for AUTOMATIC. This is the preferred selection for most Heat/Cool applications when tuning a new chamber.
Monitoring and Operating the Controller This selection results in performance tuning over the full range utilizing both Heat and Cool outputs to acquire blended tune values that are then applied to both Heat and Cool tuning parameters. Both PID sets are set to the same values. Table 4-13 Procedure for Using BLENDED TUNE at Start-up for Duplex Control Step 1 Operation Configure LSP1 2 4.11.
Monitoring and Operating the Controller Step Operation 5 Initiate Tuning 6 Tuning in operation Press Result Select “DoSLOW” or “DoFAST” in lower display. Lower Display Upper display will flash “TUNE” as long as ACCUTUNE process is operating. When process completes, tuning parameters are calculated and lower display will show “NoTune” prompt.
Monitoring and Operating the Controller 4.11.6 Error Codes Table 4-16 Procedure for Accessing Accutune Error Codes Step Operation Press 1 Select Accutune Set-up Group Setup Go to Error Code Prompt Function 2 Result Upper Display = SET Lower Display = ATUNE Upper Display = (an error code) Lower Display = ATERR Table 4-17 lists all the error codes, definitions, and fixes.
Monitoring and Operating the Controller Completing Accutune When Accutune is complete, the calculated tuning parameters are stored in their proper memory location and can be viewed in the TUNING Set up Group, and the controller will control at the local setpoint using these newly calculated tuning constants. 4.12 Fuzzy Overshoot Suppression Introduction Fuzzy Overshoot Suppression minimizes Process Variable overshoot following a setpoint change or a process disturbance.
Monitoring and Operating the Controller Set up Procedure Use the following procedure (Table 4-18) to: • select two sets, • set the switch-over value, • set tuning constant value for each set.
Monitoring and Operating the Controller Switch between two sets via keyboard (without automatic switch-over) Table 4-19 Procedure for Switching PID SETS from the Keyboard Step Operation Press 1 Select Control Set-up Group Function Result Until you see: Upper Display = (the PV value) Lower Display = PIDS X 2 or (X= 1 or 2) To change PID SET 1 to PID SET2 or Vice Versa. You can use Accutune on each set. 3 Function To accept changes. 4.
Monitoring and Operating the Controller Step Operation Press Result Lower Display = A1S1VA = Alarm 1, Setpoint 1 A1S2VA = Alarm 1, Setpoint 2 A2S1VA = Alarm 2, Setpoint 1 A2S2VA = Alarm 2, Setpoint 2 NOTES: With 3 position step control, alarms set for “output” will not function. MAN, RSP, AND FSAF selections do not have setpoint values. 3 Change a value or 4 Return to Normal Display Lower Display To change any alarm setpoint value in the upper display. 4.
Monitoring and Operating the Controller 4.16 Setting a Failsafe Output Value for Restart After a Power Loss Introduction If the power to the controller fails and power is reapplied, the controller goes through the power up tests, then goes to a user configured FAILSAFE OUTPUT VALUE.
Monitoring and Operating the Controller 4.17 Setting Failsafe Mode Introduction You can set the Failsafe Mode to be Latching or Non-Latching.
Monitoring and Operating the Controller RUN/HOLD key You can start or stop the Ramp or Program using the RUN/HOLD key. 4.19 Setpoint Ramp Introduction When you have configured a SETPOINT RAMP, the ramp will occur between the current local setpoint and a final local setpoint over a time interval of from 1 to 255 minutes. You can RUN or HOLD the ramp at any time.
Monitoring and Operating the Controller Step Operation Press Result 6 End the Ramp When the final setpoint is reached, “RUN” changes to “HOLD” in the upper display and the controller operates at the new final setpoint. 7 Disable SPRAMP See Section 3 – Configuration group “SPRAMP” for details. Power Outage If power is lost during a ramp, upon power-up the controller will be in HOLD and the setpoint value will be the setpoint value prior to the beginning of the setpoint ramp.
Monitoring and Operating the Controller 4.21 Setpoint Ramp/Soak Programming Introduction The term “programming” is used here to identify the process for selecting and entering the individual ramp and soak segment data needed to generate the required setpoint versus time profile (also called a program). A segment is a ramp or soak function which together make up a setpoint program.
Monitoring and Operating the Controller Contents Definition ATTENTION Entering “0” will imply an immediate step change in setpoint to the next soak. Ramp unit The ramp unit selection determines the engineering units for the ramp segments. The selections are: • TIME = Hours:Minutes (XX:XX) Range: 0-99 hr.:0-59 min • EU-H = Degrees/Hour OR EU-M = Degrees/Minute (Range – 0-999) Soak segments A soak segment is a combination of soak setpoint (value) and a soak duration (time).
Monitoring and Operating the Controller Contents Definition ENABL = When the program is initially changed from HOLD to RUN the present PV value is captured and used as the beginning setpoint value for the ramp segment. If the program is terminated before completion, the setpoint value will revert back to the PV value captured at the initial HOLD to RUN transition.
Monitoring and Operating the Controller Setpoint 500 SEG 8 SEG 9 SEG 4 400 SG 10 SEG 7 SEG 5 °F F 300 SEG 3 SG 11 SEG 2 SEG 6 SEG 1 SG 12 200 Time/Hours 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 20765 Figure 4-3 Ramp/Soak Profile Example Ramp/Soak Profile Example Prompt Function Segment Value Prompt Function Segment Value STRSEG Start Seg. 1 SG4 TI Soak Time 4 1 hr. ENDSEG End Seg. 12 SG5 RP Ramp Time 5 1 hr.:30 min. RP UNIT Engr.
Monitoring and Operating the Controller Program record sheet Draw your ramp/soak profile on the record sheet shown in Figure 4-4 and fill in the associated information in the blocks provided. This will give you a permanent record of your program and will assist you when entering the Setpoint data. Figure 4-4 Program Record Sheet Prompt Function Segment Value Prompt Function Segment STRSEG Start Seg. SG4 TI Soak Time 4 ENDSEG End Seg. SG5 RP Ramp Time 5 RP UNIT Engr.
Monitoring and Operating the Controller Run/Monitor the program Prior to running the program, make sure all the “SP PROG” function prompts under the Set Up group “SP RAMP” have been configured with the required data. “HOLD” appears periodically in the upper display indicating that the program is in the HOLD state. ATTENTION SP Programmer parameter cannot be changed during RUN state (must be in HOLD state). Run/Monitor functions Table 4-26 lists all the functions required to run and monitor the program.
Monitoring and Operating the Controller Function Press Viewing the present ramp or soak segment number and time Lower Display Viewing the number of cycles left in the program until you see Lower Display until you see End Program Result Upper Display = PV value Lower Display = XXHH.MM Time remaining in the SEGMENT in hours and minutes. XX = The current number, 1 to 12. Upper Display = PV value Lower Display = REC_XX Number of cycles remaining in the setpoint program.
Monitoring and Operating the Controller 4.22 P.I.E. Tool Maintenance Screens Introduction This controller uses special P.I.E. Tool® Maintenance Screens which allow remote access and access to functions not accessible via the controller’s display and keyboard. The figures in this section show screen-shots of the Maintenance Screens from the PC version of the P.I.E. Tool®. Pocket PC Maintenance Screens are generally similar in format but smaller.
Monitoring and Operating the Controller Figure 4-6 Loop Data Maintenance Screen The Loop Data screen allows you to see the current status of the process loop. The OP1, OP2 and OP3 windows indicate the status of the current outputs. If a current output is not installed, the OP status for that output is always OK. The Alarms and Digital Inputs buttons allow you to see the current status of each alarm setpoint and digital input.
Monitoring and Operating the Controller Loop Data – Alarm Details This screen appears when you click on the Alarm button on the Loop Data Maintenance Screen and shows the status of each alarm setpoint. NONE in the Type column indicates that the alarm is disabled. Highlighted alarms are currently active. An asterisk (*) indicates that the alarm has changed state since the last communications transaction. For this instrument, the Alarm On and Alarm Off columns will always be blank. See Section 3.
Monitoring and Operating the Controller Loop Data – Digital Input Details This screen appears when you click on the Digital Inputs button on the Loop Data Maintenance Screen and shows the status of each Digital Input. NONE in the Type column indicates that the Digital Input is disabled. Highlighted Digital Inputs are currently active. An asterisk (*) indicates that the alarm has changed state since the last communications transaction. This instrument has a maximum of two Digital Inputs.
Monitoring and Operating the Controller Status Data Select Status Data from the Maintenance Data menu. The Status Data screen lets you see the current status of the controller’s diagnostics. If the controller has detected a problem, this screen will show the detected problem.
Monitoring and Operating the Controller Ethernet Status Select Ethernet Status from the Maintenance Data menu. This screen only appears in instruments that have the Ethernet Communications option. Essentially, this screen shows the same Ethernet diagnostic messages as available on the controller via the lower display window. See Section 7.5 for details. The Ethernet Status screen shows the network status of the Ethernet Link. This may be accessed either via Ethernet or via Infrared communications.
Monitoring and Operating the Controller 4.23 Configuring your Ethernet Connection Introduction This controller is shipped from the factory with the address for Infrared (IR) communications set to 3, the Ethernet IP Address set to 10.0.0.2, the Ethernet Subnet Mask set to 255.255.255.0 and the Ethernet Default Gateway set to 0.0.0.0. Consult your Information Technologies (IT) representative as to how these should be configured for your installation.
Monitoring and Operating the Controller Close the IR configuration window and then single click on the Online Configuration button shown in Figure 4-12. Figure 4-12 Online Configuration Press any button on the controller’s keyboard to activate the controller’s IR port. Point your IR dongle (if using PC) or your Pocket PC’s IR port (if using Pocket PC) at the IR window on the front of the controller and then click on the Start button. The P.I.E.
Monitoring and Operating the Controller Configuring the Controller via Ethernet Communications WARNING Configuring the Controller via Ethernet Communications requires that you change your PC’s IP settings. If you have never done this before, then it is strongly recommended that you consult with your Information Technologies (IT) representative before proceeding.
Monitoring and Operating the Controller Now set your Ethernet address to 10.0.0.2 as shown in Figure 4-15. Figure 4-15 Ethernet Communications Address Close the Ethernet configuration window and then single click on the Online Configuration button. Then, click on the Start button. The P.I.E. Tool® should start uploading the configuration information from the controller as shown in Figure 4-16.
Monitoring and Operating the Controller Figure 4-16 Configuration Upload in Progress Once the upload is complete, click on the Ethernet & Email Group. Configure your Ethernet and Email parameters per Section 3.16. Once you have changed the Ethernet settings and downloaded them to your controller, you will no longer be able to communicate with it until you change the IP address in the P.I.E. Tool® to be per the controller’s new IP Address.
Input Calibration 5 Input Calibration WARNING—SHOCK HAZARD INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION. 5.1 Overview Introduction This section describes the field calibration procedures for Input 1 and Input 2. • All input actuations in every UDC2500 controller are fully factory-calibrated and are ready for configuration by the user.
Input Calibration Calibration Steps Use the following steps when calibrating an input. Step Action 1 Find the minimum and maximum range values for your PV input range from Table 5-1. 2 Disconnect the field wiring and find out what equipment you will need to calibrate. 3 Wire the calibrating device to your controller according to the set up wiring instructions for your particular input (Subsection 5.4 or 5.6). 4 Follow the calibration procedure given for Input #1 or Input #2 (Subsection 5.5 or 5.
Input Calibration Sensor Type PV Input Range °F S 0 to 3100 Range Values °C 0% 100 % –18 to 1704 –0.092 mV 17.998 mV T -300 to 700 –184 to 371 –5.341 mV 19.097 mV T (low) -200 to 500 –129 to 260 –4.149 mV 12.574 mV W5W26 0 to 4200 –18 to 2315 –0.234 mV 37.075 mV W5W26 (low) 0 to 2240 –18 to 1227 –0.234 mV 22.283 mV RP20-RP40 32 to 3216 0 to 1880 0.000 mV 4.933 mV Thermocouple Differential * –50 to 150 –46 to 66 –1.54 mV 4.62 mV –18 to 1871 –18 to 1871 0.00 mV 0.
Input Calibration Table 5-2 Voltage and Milliamp Equivalents for Input 2 Range Values Sensor Type PV Input Range Range Values 0% 100 % Linear Milliamps 4 to 20 mA 0 to 20 mA 4.00 mA 0.00 mA 20.00 mA 20.00 mA Volts 1 to 5 Volts 0 to 5 Volts 0 to 2 Volts 1.00 Volts 0.00 Volts 0.00 Volts 5.00 Volts 5.00 Volts 2.00 Volts 5.3 Preliminary Information Disconnect the Field Wiring Tag and disconnect any field wiring connected to the input (#1 or #2) terminals on the rear of the controller.
Input Calibration Type of Input Equipment Needed RTD (Resistance Thermometer Device) Milliampere, Millivolt, Volts, and Radiamatic • A decade box, with at least ± 0.02 % accuracy, capable of providing stepped resistance values over a minimum range of 0 to 1650 ohms with a resolution of 0.001 ohm. • Three insulated copper leads of equal length for connecting the decade box to the controller. • A calibrating device with at least ± 0.02 % accuracy for use as a signal source.
Input Calibration Thermocouple Inputs Using a Thermocouple Source Refer to Figure 5-3 and wire the controller according to the procedure given in Table 5-5.. Table 5-5 Set Up Wiring Procedure for Thermocouple Inputs using Thermocouple Source Step 1 Action Connect the thermocouple extension wires to the terminals for Input #1 as shown in Figure 5-3.
Input Calibration Radiamatic, Millivolts, Volts or Thermocouple Differential Inputs Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-7. Table 5-7 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts or Thermocouple Differential Inputs (Except 0-10 Volts) Step Action 1 Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 5-5. 2 Place current/voltage source at zero before switching on.
Input Calibration 0 to 10 Volts Refer to Figure 5-6 and wire the controller according to the procedure given in Table 5-8. Table 5-8 Set Up Wiring Procedure for 0 to 10 Volts Step Action 1 Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 5-6. 2 Place voltage source at zero before switching on. 3 Do not switch voltage source ON/OFF while connected to the instrument.
Input Calibration 5.5 Input 1 Calibration Procedure Preliminary Steps • Apply power and allow the controller to warm up for 30 minutes before you calibrate. • Please read Subsection 5.4 – Input 1 Set Up Wiring before beginning the procedure. • Make sure you have LOCK set to NONE. See Subsection 3.4 - Tuning Set Up Group. • See Table 5-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values. CAUTION For linear inputs, avoid step changes in inputs.
Input Calibration Step 3 Operation Press Calibrate 100 % Function Result You will see: Upper Display = APLY ( 2 ) Lower Display = IN1SPN (10003) • Adjust your calibration device to an output signal equal to the 100 % range value for your particular input sensor. See Table 5-1 for Voltage, Degrees, or Resistance equivalents for 100 % range values.
Input Calibration 5.6 Input 2 Set Up Wiring 0 to 20 mA or 4 to 20 mA Inputs – Input 2 Refer to Figure 5-8 and wire the controller according to the procedure given in Table 5-13. Table 5-11 Set Up Wiring Procedure for 0 to 20 mA or 4 to 20 mA Inputs – Input 2 Step Action 1 Connect the copper leads from the calibrator to the Input #2 terminals as shown in Figure 5-8. 2 Place current source at zero before switching on. 3 Do not switch current source ON/OFF while connected to the instrument.
Input Calibration 0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volt Inputs – Input 2 Refer to Figure 5-9 and wire the controller according to the procedure given in Table 5-12. Table 5-12 Set Up Wiring Procedure for 0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volts – Input 2 Step Action 1 Connect the copper leads from the calibrator to the Input #2 terminals as shown in Figure 5-8. 2 Place voltage source at zero before switching on. 3 Do not switch voltage source ON/OFF while connected to the instrument.
Input Calibration Procedure The calibration procedure for Input #2 is listed in Table 5-13. The numeric codes are also listed.
Input Calibration 5.8 Restore Input Factory Calibration Introduction The factory calibration constants for all the input actuation types that can be used with the controller are stored in its non-volatile memory. Thus, you can quickly restore the “Factory Calibration” for a given input actuation type by simply changing the actuation type to another type and then changing it back to the original type.
Input Calibration Step Operation Press Result or until you change the input selection in the upper display back to the proper selection. You will see: Upper Display = Original Input Selection that matches your type of sensor. Lower Display = INxTYP 4 150 Return to Normal Operation Lower Display to return to Normal operating mode. The factory calibration will be restored.
Output Calibration 6 Output Calibration 6.1 Overview Introduction This section describes the field calibration procedures for the following types of outputs: • Current Output • Auxiliary Output What's in this section? The following topics are covered in this section. TOPIC See Page 6.1 Overview 151 6.2 Current Output Calibration 152 6.3 Auxiliary Output Calibration 154 6.
Output Calibration 6.2 Current Output Calibration Introduction Calibrate the controller so that the output provides the proper amount of current over the desired range. The controller can provide an output current range of from 0 to 21 milliamperes and is usually calibrated at 4 mA for 0 % of output and 20 mA for 100 % of output, or any other values between 0 mA and 21 mA.
Output Calibration Procedure The procedure for calibrating the Current Output is listed in Table 6-2. The numeric codes are also listed. Make sure LOCK in the Tuning Set Up group is set to NONE. (See Subsection 3.4 – Tuning Set Up Group.
Output Calibration 6.3 Auxiliary Output Calibration Introduction Calibrate the controller so that the auxiliary output provides the proper amount of current over the desired range. The controller can provide an auxiliary current output range of from 0 mA to 21 mA and is usually calibrated at 4 mA for 0 % of output and 20 mA for 100 % of output or any other values between 0 mA and 21 mA.
Output Calibration Procedure The procedure for calibrating the auxiliary output is listed in Table 6-4. The numeric codes are also listed. Make sure “LOCK” in the Tuning Set Up group is set to “NONE” (see Subsection 3.4).
Output Calibration 6.4 Restore Output Factory Calibration Procedure Introduction The factory calibration constants for the Current and Auxiliary Outputs are stored in its non-volatile memory. Thus, you can quickly restore the “Factory Calibration” for those outputs by simply changing the CO RANGE or AO RANGE to the other setting and then changing it back to the original type.
Output Calibration Step Operation Press Result Upper Display = the new selection Lower Display = CRANGE (for the Current Output) - or Lower Display = ARANGE (for the Auxiliary Output) or to change the range selection in the upper display back to the proper selection.
Troubleshooting/Service 7 Troubleshooting/Service 7.1 Overview Introduction Instrument performance can be adversely affected by installation and application problems as well as by hardware problems. We recommend that you investigate the problems in the following order: • installation related problems • application related problems • hardware and software related problems and use the information presented in this section to solve them.
Troubleshooting/Service Installation related problems Read the Installation section in this manual to make sure the UDC2500 has been properly installed. The installation section provides information on protection against electrical noise, connecting external equipment to the controller, and shielding and routing external wiring. ATTENTION System noise induced into the controller will result in diagnostic error messages recurring.
Troubleshooting/Service Customer support If you cannot solve the problem using the troubleshooting procedures listed in this section, you can get technical assistance by dialing 1-800-423-9883 USA and Canada. An engineer will discuss your problem with you. Please have your complete model number, serial number, and Software version available. The model and serial numbers can be found on the chassis nameplate. The software version can be viewed under Setup Group “Status.” See Table 7-1.
Troubleshooting/Service 7.3 Power-up Tests What happens at power-up When power is applied, the controller will run three diagnostic tests. After these tests are completed, “TEST DONE” is displayed. Test Failures If one or more of these tests fail, the controller will go to the Failsafe Manual Mode, and FAILSF will flash in the lower display and a message indicating which test failed will appear in the lower display. Then, “DONE” will appear in the lower display.
Troubleshooting/Service 7.5 Background Tests Introduction The UDC2500 performs ongoing background tests to verify data and memory integrity. If there is a malfunction, a diagnostic message will be displayed (blinking) in the lower display. In the case of simultaneous malfunctions, the messages will appear in sequence in the lower display. Table 7-3 lists these background tests, the reason for their failure, and how to correct the problem.
Troubleshooting/Service Lower Display Reason for Failure How to Correct the Problem IN2RNG Input 2 out of range. The remote input is outside the range limits. Same as IN1RNG above. IN2_FL Two consecutive failures of input 2 integration. i.e., cannot make analog to digital conversion. Same as IN1FL above. CNFERR • PV low limit is > PV high limit • SP low limit is > SP high limit • Output low limit > Output high limit 1. Check the configuration for each item and reconfigure if necessary.
Troubleshooting/Service 7.6 Controller Failure Symptoms Introduction In addition to the error message prompts, there are failure symptoms that can be identified by noting how the controller displays and indicators are reacting. Symptoms Compare your symptoms with those shown in Table 7-4.
Troubleshooting/Service If the symptom still persists, refer to the installation section in this manual to ensure proper installation and proper use of the controller in your system. 7.7 Troubleshooting Procedures Introduction The troubleshooting procedures are listed in numerical order as they appear in Table 7-4. Each procedure lists what to do if you have that particular failure and how to do it or where to find the data needed to accomplish the task.
Troubleshooting/Service Procedure #1 Table 7-5 explains how to troubleshoot power failure symptoms. Table 7-5 Troubleshooting Power Failure Symptoms Step 1 What to do Check the AC line voltage. How to do it Use a voltmeter to measure the AC voltage across terminals L1 and L2 on the rear terminal panel of the controller. Check the earth ground connection. 2 Make sure the chassis plugs into the rear of the case properly.
Troubleshooting/Service Procedure #3 Table 7-7 explains how to troubleshoot Position Proportional Output failure symptoms. Table 7-7 Troubleshooting Three Position Step Control Output Failure Step What to do How to do it 1 Make certain that the controller Make Output Algorithm Set Up group function is configured for Three Position prompt OUT ALG = TPSC. Step control. Refer to Section 3.8. 2 Check the field wiring. Refer to Section 2 - Installation for details. 3 Check the output.
Troubleshooting/Service Procedure #4 Table 7-8 explains how to troubleshoot Time Proportional Output failure. Table 7-8 Troubleshooting Time Proportional Output Failure Step 1 What to do How to do it Make sure the controller is configured Make Output Algorithm Set Up group function for Time Proportional output. prompt OUTALG = RLY or RLYD. Refer to Section 3 - Configuration. 2 Check the field wiring. Make sure the NO or NC contact wiring is correct. Refer to Section 2 - Installation for details.
Troubleshooting/Service Procedure #5 Table 7-9 explains how to troubleshoot Current/Time or Time/Current Proportional Output failure. Table 7-9 Troubleshooting Current/Time or Time/Current Proportional Output Failure Step What to do How to do it 1 Make sure the controller is configured Make Output Algorithm Set Up group function for Time/Current or Current/Time prompt OUT ALG = TCUR or CURT. Proportional output. Refer to Section 3 – Configuration. 2 Check the field wiring.
Troubleshooting/Service Procedure #6 Table 7-10 explains how to troubleshoot Alarm Relay Output failure. Table 7-10 Troubleshooting Alarm Relay Output Failure Step What to do How to do it 1 Check the alarm configuration data. If it is correct, check the field wiring. Reconfigure if necessary. Refer to Section 3 - Configuration for details. 2 Check that the applicable alarm relay actuates properly depending on what you have set at prompt AxSxTYPE.
Troubleshooting/Service Procedure #7 Table 7-11 explains how to troubleshoot a Keyboard failure. Table 7-11 Troubleshooting a Keyboard Failure Step What to do How to do it 1 Make sure the keyboard is connected properly to the MCU/output and power/input boards. Withdraw the chassis from the case and visually inspect the connection. 2 Controller Keyboard or specific keys may be LOCKED OUT via the security code. Use your four-digit security code number to change the lockout level.
Troubleshooting/Service Procedure #8 Table 7-11 explains how to troubleshoot a Communications failure Table 7-12 Troubleshooting a RS-485 Communications Failure Step What to do How to do it 1 Check the Address Number, ComState and Baud Rate settings. See Section 3.13. 2 Check the field wiring and termination resistor. Using an ohm meter, check the resistance across the communications rear terminals. See Section 2.7 for wiring diagrams.
Troubleshooting/Service Procedure #9 Table 7-13 explains how to troubleshoot a Communications failure Table 7-13 Troubleshooting an Ethernet Communications Failure Step What to do How to do it 1 Check the IP address, Subnet Mask address and Gateway address settings. See the PIE Tool Manual. 2 Check if the Ethernet Connection is active. Looking into the instrument, there should be steady green LED. If this is not present, then the instrument is not seeing a valid Ethernet connection. See Section 2.
Troubleshooting/Service 7.8 Restoring Factory Configuration Introduction This procedure restores the configuration of the instrument back to the Factory Settings per Section 3.17. ATTENTION: Restoring the factory configuration overwrites all user-entered configuration changes. This procedure cannot be undone, it is a one-way process. Table 7-15 explains how to restore Factory Configuration.
Troubleshooting/Service 7.9 Software Upgrades Introduction This procedure enables software features that were not ordered from the factory. See Table 8-3 for a list of the available Software Upgrades. ATTENTION: This procedure cannot be undone, it is a one-way process. Each instrument has a unique code number sequence, so the following procedure must be performed on each instrument to be upgraded. Table 7-16 explains how to enable new software features.
Troubleshooting/Service 11 Contact your Honeywell Representative to place an order. Please have a company purchase order number available before you call. The order entry person will ask for the following information: 1. Software Upgrade Part Number you require: Dual Display with Auto/Manual – 50004634-501, or Set Point Programming (includes Dual Display and Auto/Manual) – 50004634-502 2. Model Number of your instrument(s) 3. Serial Number of your instrument(s) 4.
Parts List 8 Parts List 8.1 Exploded View Introduction Figure 8-1 is an exploded view of the UDC2500 Controller. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1. Parts not shown are listed in Table 8-2.
Parts List Table 8-1 Parts Identification Key Number Part Number 1 51453143-501 Bezel Assembly and Bezel Gasket 2 51452758-502 Display/Keyboard (with IR) 3 51452822-502 Power/Output PWA (90-264 Vac Operation) 51452822-503 Power/Output PWA (24 Vac/dc Operation) 51452810-501 Auxiliary Output/Digital Input/RS-422/485 Communications PWA 51452816-501 Auxiliary Output/Digital Input/Ethernet Communications PWA 51452801-503 MCU/Inputs PWA (with 2nd Input and IR) for Controllers 51452801-504 MCU
Parts List 8.2 Removing the chassis Insert thin screwdriver under tabs and twist slightly and gently to disengage front Using a thin screwdriver, gently twist the screwdriver to pry the side tabs from the front face. Pry just enough to release it, otherwise you’ll bend or break the tab. If you break or bend the tab and can’t reattach the front snugly, you’ll need to reattach the front using the 4 NEMA4 screws provided. See Table 2-4 page 16.
Modbus RTU Function Codes 9 Modbus RTU Function Codes 9.1 Overview This section describes the function codes needed to upload and download the configuration from a host computer into this instrument. What's in this section? The following topics are covered in this section. TOPIC See Page 9.1 Overview 180 9.2 General Information 180 9.3 Function Code 20 182 9.4 Function Code 21 186 9.
Modbus RTU Function Codes Register Address Structure Table 9-1 Integer Parameter Type Register Numbers (Dec) 1 2 3 4 5 6 7 8 9 to 13 Name Access Type = 1 Attribute NOT SUPPORTED NOT SUPPORTED Value (16 bit integer) Not Used Low Range (16 bit integer) Not Used High Range (16 bit Integer) Not Used Description Text (ASCII string) Read / Write NOT SUPPORTED NOT SUPPORTED NOT SUPPORTED NOT SUPPORTED NOT SUPPORTED NOT SUPPORTED Notes 16-bit Unsigned Integer 1 = Read Only, 2 = Read/Write Table 9-2 Floati
Modbus RTU Function Codes 9.3 Function Code 20 (14h) - Read Configuration Reference Data Description Function code 20 (14 Hex) is used in this instrument to read information stored in its configuration database. Each configuration item is explicitly addressed by a file number and register address. IEEE 32-bit floating point and 16-bit integer formats are supported. Request and Response Formats The Request and Response formats for Function code 20 (14 Hex) are shown below.
Modbus RTU Function Codes Reference Type Definitions The Reference Type definition is always 06. See examples in Subsection 9.3.1 File Number The file number word contains the register number from the register address structure tables on page 3. Although the register address structure tables indicate up to 13 data registers are available for access, only register address 3 is currently supported. Register Address The register address word represents the tag ID number for the parameter(s) being accessed.
Modbus RTU Function Codes 9.3.1 Read Configuration Examples Example #1 The following is an example of a request to read the Gain 1 value using Function code 20.
Modbus RTU Function Codes Example #2 The following is another example of a request and response message using Function code 20.
Modbus RTU Function Codes 9.4 Function Code 21 (15h) - Write Configuration Reference Data Introduction Function Code 21 (15 Hex) is used in this instrument to allow writes of integer and floating point values to the configuration database and override values. The configuration database of this instrument is located in EEROM. The override values are stored in RAM. Integer format is used to write to “Digital” configuration items.
Modbus RTU Function Codes File Number The file number word contains the register number from the register address structure shown in Table 9-1 and Table 9-2. Although the register address structure tables indicate up to 13 data registers are available for access, only register address 3 is currently supported. Register Address The register address is used to designate the tag ID number for the parameter being accessed. The register address is made up of two bytes—the MSB = 00 always.
Modbus RTU Function Codes 9.4.1 Write Configuration Examples Example #1 The following is an example of a request to write the Gain 1 value using Function code 21 (15 Hex). Request Message (Write Gain 1= 1.
Modbus Read, Write and Override Parameters plus Exception Codes 10 Modbus Read, Write and Override Parameters plus Exception Codes 10.1 Overview Introduction This section contains information concerning Reading, Writing, and Overriding parameters in this instrument. There are two types of parameters: • Data Transfer—These parameters include reading control data, option status, and reading or changing setpoints.
Modbus Read, Write and Override Parameters plus Exception Codes Analog Parameters • Whenever analog register addresses 0001 through 0074 (those that can be changed via communications) are changed, a Write cycle occurs after receipt of the message and the response is returned. Override Parameters • Override analog register address 007D (computer setpoint) is not stored in nonvolatile memory.
Modbus Read, Write and Override Parameters plus Exception Codes Table 10-1 Control Data Parameters Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Input #1 7B 123 FP RD In Engineering Units or Percentage Input #2 7C 124 FP RD In Engineering Units or Percentage PV, SP, Output 7A 122 FP RD In Engineering Units or Percentage 10.
Modbus Read, Write and Override Parameters plus Exception Codes 10.4 Miscellaneous Read Onlys 10.4.1 Register Addresses for Read Onlys The identifying register addresses listed in Table 10-3 represent some information that is Read only. No Writes allowed.
Modbus Read, Write and Override Parameters plus Exception Codes 10.5 Setpoints Overview You can use two separate local setpoints in the controller. The identifying register addresses listed in Table 10-5 allow you to select which setpoint you want to use and to enter a value in Engineering Units (whichever is selected at register address 00A1) for that setpoint via communications.
Modbus Read, Write and Override Parameters plus Exception Codes 10.6 Using a Computer Setpoint (Overriding Controller Setpoint) Overview You can use a setpoint generated from the computer to override the setpoint being used by the controller. The value generated by the computer will have ratio and bias applied by the controller. Register Addresses Use the identifying code in Table 10-7 to enter the computer setpoint.
Modbus Read, Write and Override Parameters plus Exception Codes Associated Parameters Refer to Table 10-8 for the codes to display or change any of the parameters associated with the computer setpoint.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7 Configuration Parameters Overview Listed on the next pages are the identifying codes for the parameters in the various Set-up Groups in this instrument. Most of the parameters are configurable through the hosts. Some are Read Only and are indicated as such and cannot be changed. Reading or Writing Do a Read or Write, depending on your requirements, using the identifying code and format code listed in the tables.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal 0084 132 INT R/W 0 = No Lockout 1 = Calibration Locked out 2 = +Configuration – Timer, Tuning, SP Ramp, Accutune are read/write 3 = +View – Tuning and SP Ramp are read/write, no other parameters are available 4 = Maximum Lockout Security Code 0050 080 INT R/W 0 to 9999 Man/Auto Key Lockout 00BF 191 INT R/W 0 = Disable 1
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.2 SP Ramp/Rate/Program Table 10-10 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Setpoint Ramp/Rate.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Controller Status at Program End 00B4 180 INT R/W 0 = Last Setpoint and Mode 1 = Manual, Failsafe Output Reset SP Program (ToBEGIN) 00B3 179 INT R/W 0 = Disable 1 = Via Keypad PV Hotstart 00E2 226 INT R/W 0 = Disabled 1 = Enabled Segment #1 Ramp 0039 Time 057 FP R/W 99.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Segment #8 Soak Time Data Type Access Data Range or Enumerated Selection Decimal 0044 068 FP R/W 99.59 (0-99 Hrs:0-59 Min) Segment #9 Ramp 0045 Time 069 FP R/W 99.59 (0-99 Hrs:0-59 Min) or 0 to 999 (Degrees/Minute) Segment #10 Soak Setpoint Value 0046 070 FP R/W Within Setpoint Limits Segment #10 Soak Time 0047 071 FP R/W 99.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.3 Accutune Table 10-11 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Accutune.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.4 Algorithm Table 10-12 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Algorithm.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.5 Output Algorithms Table 10-13 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Output.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.6 Input 1 Table 10-14 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Input 1.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Input 1 00A9 Transmitter Characterization 169 INT R/W 0 = B TC 1 = E TC H 2 = E TC L 3 = J TC H 4 = J TC M 5 = J TC L 6 = K TC H 7 = K TC M 8 = K TC L 9 = NNM H 10 = NNM L 11 = Nicrosil H TC 12 = Nicrosil L TC 13 = R TC 14 = S TC 15 = T TC H 16 = T TC L 17 = W TC H 18 = W TC L 19 = 100 PT RTD 20 = 100 PT LO RTD 21 = 200 PT RTD 22 =
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Burnout (Open Circuit Detection) 00A4 164 INT R/W 0 = None and Failsafe 1 = Upscale 2 = Downscale 3 = No Failsafe Emissivity 0017 023 FP R/W 0.01 to 1.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.7 Input 2 Table 10-15 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Input 2.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Input 2 00AB 171 Transmitter Characterization INT R/W 0 = B TC 1 = E TC H 2 = E TC L 3 = J TC H 4 = J TC M 5 = J TC L 6 = K TC H 7 = K TC M 8 = K TC L 9 = NNM H 10 = NNM L 11 = Nicrosil H TC 12 = Nicrosil L TC 13 = R TC 14 = S TC 15 = T TC H 16 = T TC L 17 = W TC H 18 = W TC L 19 = 100 PT RTD 20 = 100 PT LO RTD 21 = 200 PT RTD 22 = 5
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.8 Control Table 10-16 lists all the register addresses and ranges or selections for the function prompts in Set-up Group Control.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal High Output Limit 000E 014 FP R/W –5 to 105% of output Low Output Limit 000F 015 FP R/W –5 to 105% of output Output Deadband 0012 for Time Duplex 018 FP R/W –5 to +25.0% Output Deadband 0014 for TPSC 020 FP R/W 0.5 to 5.0% Output Hysteresis 0013 019 FP R/W 0.0 to 100.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.9 Options Table 10-18 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Options.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal 0 = None 1 = To Manual 2 = To Local Setpoint #1 3 = To Local Setpoint #2 4 = To Direct Action 5 = To Hold Ramp 6 = To PID Set #2 7 = To Run Ramp 8 = To Begin 9 = No I (Reset) 10 = To Manual Failsafe Output 11 = Disable Keyboard 12 = To Timer 13 = Initiate Limit Cycle Tuning 14 = Setpoint Initialization (SP=PV) 15 = To RSP 16 = Manual Lat
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.10 Communications Table 10-18 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Communications.
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.11 Alarms Table 10-19 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Alarms.
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Alarm 1 Setpoint 2 Type 008E 142 INT R/W Same as 140 Alarm 2 Setpoint 1 Type 0090 144 INT R/W Same as 140 Alarm 2 Setpoint 2 Type 0092 146 INT R/W Same as 140 Alarm 1 Setpoint 1 Event 008D 141 INT R/W 0 = Low Alarm 1 = High Alarm Alarm 1 Setpoint 2 Event 008F 143 INT R/W 0 = Low Alarm 1 = High Alarm Alarm 2
Modbus Read, Write and Override Parameters plus Exception Codes Parameter Description Register Address Hex Diagnostic Alarm 216 009A Data Type Access Data Range or Enumerated Selection Decimal 154 INT R/W 0 = Disable 1 = Alarm 1 2 = Alarm 2 UDC2500 Universal Digital Controller Product Manual 4/07
Modbus Read, Write and Override Parameters plus Exception Codes 10.7.12 Display Table 10-20 lists all the register addresses and ranges or selections for the function parameters in Set-up Group Display. Table 10-20 Set-up Group – Display Parameter Description Register Address Hex Data Type Access Data Range or Enumerated Selection Decimal Decimal Point Location 009B 155 INT R/W 0 = XXXX – Fixed 1 = XXX.X – Floating decimal point to one 2 = XX.
Modbus Read, Write and Override Parameters plus Exception Codes 10.8 Modbus RTU Exception Codes Introduction When a master device sends a query to a slave device it expects a normal response. One of four possible events can occur from the master’s query: • Slave device receives the query without a communication error and can handle the query normally. It returns a normal response. • Slave does not receive the query due to a communication error. No response is returned.
Modbus Read, Write and Override Parameters plus Exception Codes Query Example: Internal slave error reading 2 registers starting at address 1820h from slave at slave address 02. 02 03 18 20 00 02 CRC CRC Response Example: Return MSB in Function Code byte set with Slave Device Failure (04) in the data field. 02 83 04 CRC CRC Table 10-21 Modbus RTU Data Layer Status Exception Codes Exception Code Description 01 Illegal Function The message received is not an allowable action for the addressed device.
Ethernet TCP/IP 11 Ethernet TCP/IP 11.1 Overview Ethernet parameters can only be configured via the Process Instrument Explorer software. Ethernet IP Address is 10.0.0.2 as shipped from the Factory. The MAC address is printed on the case label of each instrument. When constructing a network, it is recommended that a Switch be used to connect UDCs to a LAN rather than using a Hub.
Further information 12 Further information 12.1 Modbus RTU Serial Communications Refer to Honeywell document 51-52-25-66 Modbus RTU Serial Communications User Manual. 12.2 Modbus Messaging on TCP/IP Refer to Honeywell document 51-52-25-121 MODBUS Messaging on TCP/IP Implementation Guide. 12.3 How to Apply Digital Instrumentation in Severe Electrical Noise Environments Refer to Honeywell document 51-52-05-01 How to Apply Digital Instrumentation in Severe Electrical Noise Environments.
Index 13 Index A Aborting Accutune, 109 Accutune Error Codes, 109 Accutune Error Status, 45 Accutune Iii, 104 Accutune Set Up Group, 43, 82 Adaptive Tune, 44 Alarm Blocking, 81 Alarm Hysteresis, 80 Alarm Outputs, 9 Alarm Relay Output Failure, 170 Alarm Relays, 14 Alarm Setpoints, 112 Alarm Setpoints Display, 112 Alarms Set Up Group, 76 Algorithm Set Up Group, 46 Analog Inputs, 8 Annunciators, 93 Application Related Problems, 159 Atune Group, 44, 82 Auto/Manual Key, 92 Automatic With Local Setpoint, 100 Aut
Ethernet Communications Address, 133, 134 Ethernet Configuration Screen, 84 Ethernet Connection, 131 Ethernet Status, 130 Ethernet TCP/IP, 220 Ethernet TCP/IP Communications Interface, 10 External Interface Option Connections, 29, 30 External Setpoint Program Reset, 70 External Wiring, 18 F Factory Calibration, 149, 156 Failsafe Function Prompt, 114, 115 Failsafe Manual Mode, 161 Failsafe Mode, 66 Failsafe Mode, 115 Failsafe Output Value, 65 Failsafe Output Value, 114 Failsafe Output Value For Restart After
Option Status, 191 Output Algorithm, 51 Output Calibration, 151 Output Limit, 65 Output Set Up Group, 51 Overriding Controller Setpoint, 194 P, Q P.I.E. Tool, 131 P.I.E. Tool Ethernet And Email Configuration Screens, 84 P.I.E.
Software Version Number, 160 Solid State Relay Output, 25 SP Ramp Set Up Group, 39 SP Tuning, 43 Specifications, 8 Spprog, 41 Sprate, 40 Start Segment Number, 119 Start Up Procedure For Operation, 99 Station Address, 73 Status Data, 129 Status Tests, 161 Stray Rejection, 8 Suppression Devices, 18 Switch Between Two Sets Via Keyboard, 112 Switching Between Setpoints, 102 Troubleshooting/Service, 158 Tune, 44, 104 Tune For Duplex (Heat/Cool), 105 Tuning, 35 Tuning Indicators, 104 Tuning Parameter Sets, 61 Tu
Sales and Service 14 Sales and Service For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
4/07 UDC2500 Universal Digital Controller Product Manual 227
228 UDC2500 Universal Digital Controller Product Manual 4/07