Product manual

Configuration
42 UDC2500 Universal Digital Controller Product Manual 4/07
Function Prompt
Lower Display
Selection or Range of Setting
Upper Display
English Numeri
c Code
English Numeric
Code
Parameter
Definition
STATE 214 DIS
HOLD
0
1
Program State at Program End
ToBEGN 215 DIS
KEY (Keyboard)
0
1
Reset/Rerun SP Program
PVSTRT 216
DIS
ENAB
0
1
DISABLE—LSP1 is used as the initial ramp
setpoint.
ENABLE—Current PV value is used as the
initial ramp setpoint.
SG1 RP
SG3 RP
SG5 RP
SG7 RP
SG9 RP
SG11 RP
217
220
223
226
229
232
0-99hours:0-
59minutes
Engineering
Units/minute or
Engineering Units
/hour
Segment #1 Ramp Time or
Segment #1 Ramp Rate
Select TIME, EU-M, or EU-H at prompt
RPUNIT. All ramps will use the same
selection.
SG2 SP
SG4 SP
SG6 SP
SG8 SP
SG10SP
SG12SP
218
221
224
227
230
233
Enter a Value
within the Setpoint
Limits
Soak Segments Setpoint Value
SG2 TI
SG4 TI
SG6 TI
SG8 TI
SG10TI
SG12TI
219
222
225
228
231
234
0-99 Hours:0-59
Minutes
Soak Segments Duration