Submittal Sheet

MINIMUM TEMPERATURE OF
CONTROL AGENT
40 F
(4
C).
DISC
Removable composition.
SEAT
Removable brass.
PLUG
Removable stainless steel.
STEM
Removable stainless steel.
RECOMMENDED FITTINGS
Standard 45 degree SAE flare nuts.
OPERATOR
OPERATING RANGE
9 to 13
lb/in2
(60
to 90
kPa),
non-
adjustable.
DIAPHRAGM
Molded neoprene rolling type, 11 square
inch
I.007
meters
2
)
effective area.
MAXIMUM SAFE AIR PRESSURE
25
lb/in2
(172 kPa).
MAXIMUM PRESSURE FOR CLOSE-OFF
(With Operator Pressure 2
lb/in2
[I4
kPa1
Below Spring
Rangei
50
lb/in2
(345 kPa).
All? CONNECTION
Push-on barb for 5132 or
l/4
in.
(4
or 6
mm) 0.0. plastic tubing.
MAXIMUM SAFE DIAPHRAGM
TEMPERATURE
160 F (71 C).
An increase in control-air pressure
moves the valve toward the open posi-
tion permitting the control agent to
flow through the system coil.
FIG. 2.
VP513B
TYPICAL OPERATION
HONEYWELL*Minneapolis,
Minnesota
55408*Scarborough,
Ontario%ubsidiaries
and Affiliates Around the
World.*Printed
in U.S.A.