Service Manual

14
2. Sequence Flow Charts
a) Refrigerator
Refrigerator Sequence Flow Chart
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
1. Startup/Cool Down
2. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
MH energized
CTh in control
Slight
Delay at
Startup
CTh cools
to 3°F (1.7°C)
below setpoint.
Factory default
36°F (2°C)
CTh warms
to 3°F (1.7°C)
above
setpoint
4. Defrost
DTh cools to
8.6°F(-13°C)
EvapFM energized
MH energized
Comp de-energized
ConFM de-energized
5. Defrost Termination
DTh warms to
40°F (4.4°C)
Note:
a) EvapFM de-energizes when door is opened on FS and when
upper door is opened on HS.
b) 2-minute minimum Comp on timer starts when Comp energizes.
c) 2-minute minimum Comp off timer starts when Comp de-energizes.
d) 2-minute temperature display delay timer starts when defrost
termination temperature is met.
e) 20-minute minimum defrost time.
f) 1-hour maximum defrost time.
DTh in control
Power on
EvapFM energized
MH energized
Comp de-energized
ConFM de-energized
2-min. Comp off
timer starts
EvapFM energized
MH energized
2-min. Comp on
timer starts
2-min. temperature display
delay timer starts
Comp energized
ConFM energized
EvapFM energized
MH energized
3. Cool Down Restart