Manual

9
Dorgard Operation and Self Test
To hold the door open:
1. Open the door to the required position.
2. Stand sideways to the door.
3. Depress the Plunger down using your foot. Greater
foot pressure may be needed depending upon the
force from the door closer or the type of floor surface.
4. Whilst depressing the Plunger, push/pull the door
gently in the direction of closing.
5. Remove your foot and let go of the door.
To release Dorgard, either:
A. Lightly tap the Plunger towards the fire door with
your foot.
or;
B. Push the door in the direction of opening.
Note. If the door has been pushed hard against
the Floorplate Bump Stop or a wall, then
Dorgard will only release by method A.
Self Test:
Dorgard conducts weekly Self Tests 12 hours after
Battery installation and then every 7 days after that.
During the Self Test, if the fire door is being retained,
Dorgard will release the door. Should Dorgard detect
an internal fault it will sound a warning tone and Fail
to Safe.