HP BladeSystem c7000 Carrier-Grade Enclosure Maintenance and Service Guide

7 Specifications
Environmental specifications
ValueSpecification
Temperature range
1
5°C to 40°C (41°F to 104°F)Operating
-30°C to 60°C (-22°F to 140°F)Non operating
-5°C to 50°C (23°F to 122°F)Short-term
Wet bulb temperature
28ºC (82.4ºF)Operating
38.7ºC (101.7ºF)Non operating
Relative humidity (noncondensing)
2
20% to 80%Operating
5% to 95%Non-operating
1
All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m (1.8°F per 1000 ft) to 3048
m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1
psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage
corresponds to a pressure minimum of 70 KPa.
Rack specifications
Value
Specification
1
36UU Height
26.7 in (67.8 cm)Width
39.4 in (100.0 cm)Depth
Top, BottomCable Entry
1200 lbs (544.3 kg)Max Load
500 lbs (226.8 kg)
485 lbs (219.9 kg) - R2 rack
Rack Weight
200 lbs (90.7 kg)Packaging and Pallet Weight
1
Including side panels.
Floor space requirements
RecommendedMinimum
Measurement cmincmin
13051.291.436Front (appearance side) clearance
13051.291.436Rear (service side) clearance
< 2.5< 1.0----Space between cabinets
68.627----Cabinet pitch
Environmental specifications 25