HP OneView Deployment and Management Guide 1.0

Technical white paper | HP OneView Deployment and Management Guide
61
2. To add HP iPDUs that power your previously discovered equipment, on the Power Deliver Device screen select + Add
power delivery device.
3. Enter the FQDN or IP address along with the login creditials needed for discovery.
4. Once the iPDUs have been discovered, view the rack in which the iPDU-powered equipment resides. The iPDUs will be
automatically depicted in the rack layout.
5. Edit the rack associated with the iPDU to set the iPDU core position properly.
6. Drag the iPDU to the upper or lower 0U space drop zones on the A/B side of the rack as appropriate.
7. Or specify the position via the device configuration popup accessible via the gear icon on the device.