HP XP7 Owner Guide (H6F56-96006)

6 System specifications and requirements
This section describes the physical characteristics of XP7 Storage, including
“Mechanical specifications” (page 78)
“Electrical specifications” (page 78)
“Environmental specifications” (page 82)
Mechanical specifications
The following table lists the mechanical specifications of XP7 Storage.
Table 21 XP7 mechanical specifications
Six RacksFive RacksFour RacksThree RacksTwo RacksOne RackDimension
142 inches118.5 inches95 inches71.3 inches47.6 inches24.0 inchesWidth
(3610 mm)(3010 mm)(2410 mm)(1810 mm)(1210 mm)(610 mm)(includes 1 set of
side panels)
45 inches45 inches45 inches45 inches45 inches45 inchesDepth
(1145 mm)(1145 mm)(1145 mm)(1145 mm)(1145 mm)(1145 mm)(including doors)
79 inches79 inches79 inches79 inches79 inches79 inchesHeight
(2006 mm)(2006 mm)(2006 mm)(2006 mm)(2006 mm)(2006 mm)(including casters)
7500 / 34023750 / 17011120 / 508
(Diskless)
Min (lbs /
kg)
System
Weight
8560 / 38834319 / 19591558 / 707Max (lbs /
kg)
NOTE: Each Rack is 600mm wide without side covers. Add 5mm to each end of entire assembly
for each side cover.
Electrical specifications
“System heat and power specifications” (page 78) and “System components heat and power
specifications ” (page 79) list the heat and power specifications for XP7 Storage and components.
Table 22 System heat and power specifications
Full Array (DKC-0
plus DKC-1 plus
DKU x4)DKU RackDKC Module-1DKC Module-0
Parameter
1, 2
33.15.455.425.87Max Power
consumption (kVA)
Heat Dissipation
and Power
Consumption
31.45.175.155.57Max Heat
dissipation (kW)
Specifications
(Maximum
configuration)
107155176431757119012Max BTUs per
hour
27002444644284791Max Kcal per hour
1
Heat (KW, BTU, Kcal) and Power (kVA) values are for determining load for site planning. Actual heat generation
and power demand may be less.
2
Calculated values with drives at a typical I/O condition. (Random Read and Write, 50 IOPSs for HDD, 2500 IOPSs
for SSD, Data Length: 8Kbytes). These values may increase for future compatible drives.
78 System specifications and requirements