HP XP7 Owner Guide (H6F56-96006)

Table 23 System components heat and power specifications (continued)
Power Consumption
(kVA)
1
Heat Output (kW)
1
HP XP7 Storage ComponentComponent Product Number
2
Power is consumed during the battery back-up time only.
3
Actual values at a typical I/O condition. (Random Read and Write, 50 IOPSs for HDD, 2500 IOPSs for SSD, Data
Length: 8 KB). These values may increase for future compatible drives.
4
Maximum values with all fans rotate at maximum.
5
Base Drive Chassis does not include power supplies consequently demands zero (0) kVA and generates no (0) kW
heat.
NOTE: Site power can be connected to the PDUs at either the top or bottom of the racks.
Grounding
The site and equipment must meet all of the following three conditions of installation for grounding.
An insulated grounding conductor that is identical in size and insulation material and thickness
to the grounded and ungrounded branch-circuit supply conductors. It must be green, with or
without yellow stripes, and must be installed as a part of the branch circuit that supplies the
unit or system.
The grounding conductor mentioned above should be grounded to earth at the service
equipment or other acceptable building earth ground such as the building frame in the case
of a high rise steel-frame structure.
The attachment-plug receptacles in the vicinity of the unit or system must include a ground .
The grounding conductors serving these receptacles must be connected to earth ground at the
service equipment or other acceptable building earth ground such as the building frame in
the case of a high-rise steel-frame structure.
Power connection
The AC power input for XP7 Storage has a duplex PDU structure. This duplex structure enables the
entire rack to remain powered on if power is removed from one of the two power distribution
panels.
CAUTION: When installing a system, connect the AC cables between the PDUs and PDPs correctly.
Otherwise, a system failure can occur when one of the AC inputs is interrupted.
AC Power - PDU Options
XP7 is configured for input power using separate rackmount PDU products. PDUs are available
for three phase or single phase power for NEMA and IEC compliance applications.
NOTE: When ordering systems, HP does not allow mixtures of different phase PDUs in a system
(even though there are no technical issues). Only upgrade orders can ship with difference phase
PDUs in a system.
Table 24 XP7 AC PDU Options
Notes
Facility
receptacle
neededPlug Type
Branch circuit
requirements
per PDU
Number of
PDU per Rack
1
Local Power
Product
Number
For customers
with, 200 - 220
NEMA
L15-30R
NEMA
L15-30P
200-220V, 3Ø,
4-wire, 30A
23 phase (4
wire)
H6F71A
VAC, 3-Phase,
4-Wire Power
80 System specifications and requirements