Table 24 XP7 AC PDU Options (continued)
Notes
Facility
receptacle
neededPlug Type
Branch circuit
requirements
per PDU
Number of
PDU per Rack
1
Local Power
Product
Number
Distribution
System
For customers
with 380 - 415
IEC60309 4
pole, 5-wire,
IEC60309 4
pole, 5-wire
380-415V, 3Ø,
5-wire, 16A
23 phase (5
wire)
H6F73A
VAC,380-415 VAC,
16A
380-415VAC,
16A Three-Phase,
5-Wire Wye
Power
Distribution
System
For customers
with single
NEMA L6-30RNEMA L6-30P200-240V, 1Ø,
3-wire, 30A
4single phase
NEMA
H6F70A
phase power
and need
NEMA L6-30P
plug
For customers
with single
IEC60309 2
pole, 3-wire,
240VAC, 32A
IEC60309 2
pole, 3-wire,
240VAC, 32A
200-240V, 1Ø,
3-wire, 32A
4single phase
IEC
H6F72A
phase power
and need
IEC60309 32A
plug
Notes
1. Each PDU has one fixed power cord with attached plug. Power cord is not removable.
NOTE:
• PDU models can be changed in the field by ordering the upgrade PDU model required.
• PDU models can be changed in the field using offline maintenance procedures.
• When ordering systems, HP does not allow mixtures of different phase PDUs in a system (even
though there are no technical issues). Only upgrade orders can ship with difference phase
PDUs in a system.
Table 25 Requirements for Input Voltage and Input Frequency
Tolerance (%)ConditionsInput Voltages (AC)Frequency
+6 % or -8 %1 Phase 2 Wire + Ground200V - 240V60Hz ± 2Hz
+6 % or -8 %1 Phase 2 Wire + Ground200V - 240V50Hz ± 3Hz
NOTE: This unit does not apply to IT power system.
Electrical specifications 81