Environmental Monitoring Unit
UltraSCSI RAID Enclosure 3–11
Note
For detailed instructions about using the
set emu
commands, refer to the array controller CLI documentation.
Table 3–2 EMU Set Point Temperature Conversions
°F °C °F °C °F °C °F °C °F °C
32 0 50106820863010440
34 1 52117021883110641
36 2 54127222903210842
37 3 55137323913310943
39 4 57147524933411144
41 5 59157725953511345
43 6 61167926973611546
45 7 63178127993711747
46 8 64 18 82 28 100 38 118 48
48 9 66 19 84 29 102 39 120 49
Table 3–3 Temperature Set Point Rules—EMU Firmware
Versions 1.0 and 1.1
1. Enter all temperatures in degrees Celsius (°C). Do not use fractions,
decimals, or degrees Fahrenheit (°F).
2. The EMU set point (sensor_3) temperature must be a minimum of
6°C (11°F)
greater than
the highest expected ambient (intake)
temperature.
3. The backplane set points (sensor_1 and sensor_2) must be the same
temperature and a minimum of 13°C (23°F)
greater than
the highest
expected ambient temperature. This requires a minimum setting of
7°C (13°F)
greater than
the EMU set point.