HP StorageWorks Data Replication Manager HSG80 ACS Version 8.7P Configuration Guide (AA-RPHZF-TE, March 2004)

Configuring a Standard Data Replication Manager Solution
105Data Replication Manager HSG80 ACS Version 8.7P Configuration Guide
Example Display 29
.
.
.
Mirrored Cache:
256 megabyte write cache, version 0012
Cache is GOOD
No unflushed data in cache
.
.
.
Note: These settings are applied automatically to controller B2. It is not necessary to repeat these
steps on controller B2.
L
I 19. Set the fabric topology for each port on both controllers by issuing the following CLI
commands:
Note: You may be prompted to restart the controllers after each command, but you do not need
to restart the controllers until all topologies have been set.
SET THIS_CONTROLLER PORT_1_TOPOLOGY=FABRIC
SET THIS_CONTROLLER PORT_2_TOPOLOGY=FABRIC
SET OTHER_CONTROLLER PORT_1_TOPOLOGY=FABRIC
SET OTHER_CONTROLLER PORT_2_TOPOLOGY=FABRIC
I 20. Issue the following CLI command:
SET LOG NOLOG
Note: You can ignore the error message ERROR B020:No Logdisk is Configured if it
appears.
I 21. Restart the controllers in the order shown:
RESTART OTHER_CONTROLLER
RESTART THIS_CONTROLLER
Note: There may be a brief delay before control is returned.
I 22. After the controllers have restarted, verify that the topology is set correctly:
SHOW THIS_CONTROLLER
SHOW OTHER_CONTROLLER
You should see a display similar to that in Example Display 30.