HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software Maintenance and Service Guide (EK-G80MS-SA. C01, March 2005)

Replacing BA370, M2100 & M2200 Enclosure Elements
144 HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software
Maintenance and Service Guide
Figure 59: Install Options screen
e. Enter 3 to install the other cache module.
The Slot Designations screen is displayed.
f. Enter Y(es) to confirm the intent to install the slot x cache module.
FRUTIL quiesces all device ports, indicates a time limit of 2 minutes
to install the replacement cache module, and then begins displaying
the time remaining in 10-second intervals.
Caution: Wait for
FRUTIL
to quiesce the device ports—indicated by an All
device ports quiesced message. Failure to allow the ports to quiesce
can result in data loss. Quiescing can take several minutes.
Note: A countdown timer allows you a total of 2 minutes to install the cache module.
After 2 minutes, “this controller” exits
FRUTIL
and resumes operations. If this happens,
return to substep 2b and proceed.
H 3. For the replacement cache module, complete the following substeps:
H a. Carefully align and partially insert the cache module in the
appropriate guide rails.
Caution: Misalignment of the cache module in the guide rails can damage
the backplane.
Install Options:
1. Other controller and cache module
2. Other controller module
3. Other cache module
4. Exit
NOTE: OPTION 1 DISABLED (So: Do cache, then controller.)
Enter choice: 1,2,3,4 ->