HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software Maintenance and Service Guide (EK-G80MS-SA. C01, March 2005)

Replacing BA370, M2100 & M2200 Enclosure Elements
154 HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software
Maintenance and Service Guide
7. Press Enter or Return.
The ECB expiration date and deep discharge history are updated. FRUTIL
exits.
8. If you are replacing the ECB for an array controller in a M2200 enclosure,
proceed to step 10.
9. For a dual-redundant controller configuration with a dual ECB installed:
a. If the “other controller” cache module is also to be connected to the
replacement ECB, connect the PC or terminal to the “other controller”
maintenance port.
The connected array controller now becomes “this controller.”
b. Repeat step 3 (starting on page 151) through step 7.
c. Remove the old dual ECB and place the replacement ECB in that
location.
10. Disconnect the PC or terminal from the array controller maintenance port.
11. If you are replacing the ECB for an array controller in a M2200 enclosure,
repeat step 1 (on page 151) through step 9 to replace another ECB for the
“other controller” in a dual-redundant controller configuration.