HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software Command Line Interface Reference Guide (EK-G80CL-RA. C01, March 2005)

CLI Command Descriptions
209HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software
Command Line Interface Reference Guide
FANSPEED=HIGH
FANSPEED=AUTOMATIC
(default)
Sets the speed at which the fan operates.
Select FANSPEED=HIGH to force the fans in all connected enclosures to
operate at high speed continuously.
Select FANSPEED=AUTOMATIC to allow the EMU to control the fan
speed for the fans in all connected enclosures.
The EMU instructs the fans to operate at high speed if any of the temperature
setpoints are exceeded or if one or more fans are not functioning. Refer to
Table 7 on page 210 for additional information on setpoints.
SENSOR_1_SETPOINT=nn
SENSOR_2_SETPOINT=nn
SENSOR_3_SETPOINT=nn
SENSOR_x_SETPOINT=35
(default)
Sets the acceptable temperatures (in Celsius) at which the subsystem operates.
Sensor 1 and Sensor 2 set the maximum operating temperature for the
primary subsystem enclosure. Sensor 3 sets the maximum operating
temperature for the EMU unit. The allowable range for the setpoint is 0°C
(32°F) to 49°C (120°F). The EMU determines the default setpoint for all three
sensors. Refer to Table 7 on page 210 for additional information on setpoints.