HP StorageWorks HSG80 ACS Solution Software V8.8 for Windows NT, Windows 2000, and Windows Server 2003 (32-bit) Installation and Configuration Guide (AA-RV1XA-TE, March 2005)

FC Configuration Procedures
161HSG80 ACS Solution Software V8.8 for Windows NT, Windows 2000, and Windows Server
2003 (32-bit) Installation and Configuration Guide
2. Use the FRUTIL utility to set up the battery discharge timer. Enter the
following command to start FRUTIL:
RUN FRUTIL
When FRUTIL asks if you intend to replace the battery, answer “Y”:
Do you intend to replace this controller's cache battery? Y/N
[N] Y
FRUTIL will print out a procedure, but will not give you a prompt. Ignore the
procedure and press the Enter key.
3. Set up any additional optional controller settings, such as changing the CLI
prompt. See the SET THIS CONTROLLER/OTHER CONTROLLER
command in the HP StorageWorks HSG60 and HSG80 Array Controller and
Array Controller Software Command Line Interface (CLI) Reference Guide
for the format of optional settings.
4. Verify that all commands have taken effect. Use the following command:
SHOW THIS
Verify node ID, allocation class, SCSI version, failover mode, identifier, and
port topology.