Fabric OS Administrator's Guide v7.0.0 (53-1002148-02, June 2011)

472 Fabric OS Administrator’s Guide
53-1002148-02
Backbone fabric IDs
23
---------------------------------------
SCC - accept
DCC - accept
PWD - accept
Fabric-Wide Consistency Policy :- "SCC:S;DCC"
If the Fabric Wide Consistency Policy has the letter “S” in it in the edge fabric or the backbone
fabric, do not connect the edge fabric to the FC router. The letter “S” (shown in the preceding
sample output) indicates the policy is strict. The fabric-wide policy must be tolerant before you
can connect fabrics to the FC router. See Chapter 7, “Configuring Security Policies for
information about configuring the fabric-wide consistency policy.
5. For 8-Gbps platforms, delete fabric mode Top Talker monitors, if they are configured. See
“Deleting all fabric mode Top Talker monitors” on page 409 for instructions.
FC-FC routing and fabric mode Top Talker monitors are not concurrently supported on 8 Gbps
platforms.
FC-FC routing and fabric mode Top Talker monitors are concurrently supported only on the
Brocade 6510 and on the Brocade DCX family with only 16 Gbps-capable ports.
Backbone fabric IDs
If your configuration has only one backbone fabric, then this task is not required because the
backbone fabric ID in this situation defaults to a value of 128. The default backbone fabric ID is 1 if
Virtual Fabrics is disabled.
All switches in a backbone fabric must have the same backbone fabric ID. You can configure the
backbone fabric ID using the fcrConfigure command. The backbone fabric ID must be unique from
the perspective of every attached edge fabric. Fabric ID changes made on a switch are not
propagated to other switches in the backbone fabric. Rather, the backbone fabric administrator is
responsible for making sure that all switches in the backbone have the same fabric ID. Because
fabric IDs are used heavily by the routing protocol between the Fibre Channel routers, using the
wrong fabric ID can affect both edge-to-edge and backbone-to-edge routing.
In addition to ensuring that the backbone fabric IDs are the same within the same backbone, you
must make sure that when two different backbones are connected to the same edge fabric, the
backbone fabric IDs are different, but the edge fabric ID should be the same. Configuration of two
backbones with the same backbone fabric ID that are connected to the same edge is invalid. In this
configuration, a RASLog message displays a warning about fabric ID overlap. When two backbone
fabrics are not connected to the same edge, they can have the same backbone fabric ID.
ATTENTION
In a multi-switch backbone fabric, modification of FID within the backbone fabric will cause
disruption to local traffic.
Assigning backbone fabric IDs
1. Log in to the switch or director.
2. Enter the switchDisable command if EX_Ports are online.
3. Enter the fosConfig
--disable fcr command to disable the FC-FC Routing Service.
The default state for the FCR is disabled.