Managing Superdome Complexes: A Guide for HP-UX System Administrators

Managing the Overall Complex
Detecting / Controlling Power in the Complex
Chapter 386
The following example shows cabinet power details for cabinet 0 of an
SD64000 model Superdome server.
HP-UX Commands The frupower, parstatus, and rad commands enable you to check
Superdome power status from HP-UX.
This procedure describes how to use these HP-UX commands to check
cabinet, cell, and I/O chassis, and PCI card slot power details.
Step 1. Log in to HP-UX running on one of the Superdome complex’s partitions.
You can check the power status for cabinets, cells, and I/O chassis from
any partition.
To check the power status for PCI card slots, you must log in to the local
partition where the corresponding PCI card cage resides.
Select Device: b
Enter cabinet number: 0
HW status for SD64000 compute cabinet #0: NO FAILURE DETECTED
Power switch: on; Power: enabled, good; Door: closed
Fan speed: normal; Temperature state: normal
Redundancy state: fans or blowers redundant, BPSs redundant
| Main BP| | IO Backplanes |
| Power | | IO Bay 0 | IO Bay 1 |
| Main | Boards | Cells | Chassis | Chassis |
| BP | 0 1 2 | 0 1 2 3 4 5 6 7 | 0 1 2 3 | 0 1 2 3 |
+--------------+------+--------+-----------------+----------+----------+
Populated | * | * * * | * * * * * * * * | * * | |
Power Enabled | * | * * * | * * * * * * * * | * * | |
Powered On | * | * * * | * * * * * * * * | * * | |
Power Fault | | | | | |
Attention LED | | | * | * | |
| Cabinet | IO |
| BPS | Blowers | Fans |
| 0 1 2 3 4 5 | 0 1 2 3 | 0 1 2 3 4 |
+-----------+-------------+---------+-----------+
Populated | * * * * * | * * * * | * * * * * |
Failed | | | |
PM firmware rev 6.6, time stamp: FRI SEP 08 19:36:47 2000
CLU firmware rev 6.10, time stamp: WED SEP 06 20:56:50 2000
GSP:CM>