Network Card User's Manual

#AASiCj
Command
#AASiCj
Description
Reads the analog input or counter/frequency module data from
specified slot and the specified channel in the I-8000 unit.
#AASiCj[CHK](cr)
# A delimiter character
AA A 2-character HEX module address for the
specified I-8000 unit, ranging from 01 to FFh
Si The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)
Cj specified channel number.
i-87013 Î j = 0 to 3
i-8017H Î j = 0 to 7
i-87017 Î j = 0 to 7
i-87018 Î j = 0 to 7
i-8080 Î j = 0 to 7
[CHK] The 2-character of Checksum
Syntax
(cr) Carriage Return(0x0D) for denote the end of the
command
Valid Command >(data)[chk](cr)
Invalid Command ?AA[CHK](cr)
Any syntax or communication error may receive no response.
> A delimiter for valid command
? A delimiter for invalid command
AA A 2-character HEX module address
(data) A return string from RTD input module in
engineering mode.
[CHK] A 2-character checksum
(cr) Carriage Return (0x0D) to denote the end of the
response
Command
#01S3C0
Response
>+2.1234(cr)
Example
Description The data read from the analog data input module
in slot 3 and channel 0 of the I-8000 unit at address
01h is +2.1234.
Notes: i-87013 Î 4-Channel RTD Analog Input Module
i-8017H Î Fast 8-Channel mV/V/mA Analog Input Module
i-87017 Î 8-Channel mV/V/mA Analog Input Module
i-87018 Î 8-Channel mV/V/mA and Thermocouple Analog Input
Module
i-8080 Î 8-Channel Counter/Frequency Module
8430/8830/8KE4/8KE8 Users manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 73