Installation Guide

PowerPlug
®
Luminaire Disconnect -
Model 103 Installation Instructions:
To be sold only with installation instructions.
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires. Do not
exceed maximum current and voltage levels.
Instructions:
Conductor installation:
1. Wiring must comply with all applicable electrical codes.
2. Turn off power before removing or installing disconnect.
3. Strip wires to 3/8” (9,5 mm). 18 AWG can be
3/8” to 1/2” strip.
4. Grip load wires firmly and push conductors into
white cap ports. See load side diagrams at right for
proper wire insertion for ballast configurations.
5. Grip supply wires firmly and push conductors into ports opposite load wires. See line side
diagram at right for proper wiring configuration.
6. Use only one conductor per port and assure that no copper is exposed on any of the wires
inserted.
7. See disconnect de-mate/mate installation instructions below when replacing ballasts.
8. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT
REMOVE AND REPLACE WIRES.
DANGER
NEVER remove wires from product as contact with electricity can cause serious injury or
death. Shut off power at the circuit breaker or remove fuse when installing this product.
SAFETY NOTICE
Improperly installed electrical wiring can be dangerous and cause electrical fires. This product
must be used in accordance with the current rating and wire sizes listed. Consult local building
code before doing any electrical work.
PowerPlug
®
Luminaire Disconnect -
Model 103 Installation Instructions:
To be sold only with installation instructions.
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires. Do not
exceed maximum current and voltage levels.
Instructions:
Conductor installation:
1. Wiring must comply with all applicable electrical codes.
2. Turn off power before removing or installing disconnect.
3. Strip wires to 3/8” (9,5 mm). 18 AWG can be
3/8” to 1/2” strip.
4. Grip load wires firmly and push conductors into
white cap ports. See load side diagrams at right for
proper wire insertion for ballast configurations.
5. Grip supply wires firmly and push conductors into ports opposite load wires. See line side
diagram at right for proper wiring configuration.
6. Use only one conductor per port and assure that no copper is exposed on any of the wires
inserted.
7. See disconnect de-mate/mate installation instructions below when replacing ballasts.
8. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT
REMOVE AND REPLACE WIRES.
DANGER
NEVER remove wires from product as contact with electricity can cause serious injury or
death. Shut off power at the circuit breaker or remove fuse when installing this product.
SAFETY NOTICE
Improperly installed electrical wiring can be dangerous and cause electrical fires. This product
must be used in accordance with the current rating and wire sizes listed. Consult local building
code before doing any electrical work.
COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105°C (221°F)
maximum. Flame Rated UL94V-0.
This disconnect is rated for 600 Volts/6 Amps maximum.
Rated for a limited number of current-interrupting operations.
Wire Range Line Side (Orange) Load Side (White)
Solid: 12-18 AWG 18 AWG
Stranded: 12-14 AWG (19 Strand or less)
Stranded Tin Bonded: 12-14 AWG (19 Strand or less) 18 AWG
16 AWG (26 Strand or less) (16 Strand or less)
18 AWG (16 Strand or less)
Disconnect de-mate / mate installation
1. To de-mate, grasp disconnect at each end and pull apart to separate the disconnect halves.
Do NOT pull on wires.
2. To mate the disconnect, grasp each disconnect half, align halves, and push together.
IDEAL INDUSTRIES, INC.
1375 Park Avenue
Sycamore, IL 60178, U.S.A.
800-435-0705 Customer Assistance
www.idealind.com
ND
6847-7
Hot
BALLAST
BALLAST
BALLAST
BALLAST
Line Side (3 Ports)
(Orange Cap)
Load Side (6 Ports)
(White Cap)
Single Ballast
(Red)
Switchable/Step
Dimming
Full-Light Output
Neutral
Hot #2
(Red)
BALLAST
COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105°C (221°F)
maximum. Flame Rated UL94V-0.
This disconnect is rated for 600 Volts/6 Amps maximum.
Rated for a limited number of current-interrupting operations.
Wire Range Line Side (Orange) Load Side (White)
Solid: 12-18 AWG 18 AWG
Stranded: 12-14 AWG (19 Strand or less)
Stranded Tin Bonded: 12-14 AWG (19 Strand or less) 18 AWG
16 AWG (26 Strand or less) (16 Strand or less)
18 AWG (16 Strand or less)
Disconnect de-mate / mate installation
1. To de-mate, grasp disconnect at each end and pull apart to separate the disconnect halves.
Do NOT pull on wires.
2. To mate the disconnect, grasp each disconnect half, align halves, and push together.
IDEAL INDUSTRIES, INC.
1375 Park Avenue
Sycamore, IL 60178, U.S.A.
800-435-0705 Customer Assistance
www.idealind.com
ND
6847-7
Hot
BALLAST
BALLAST
BALLAST
BALLAST
Line Side (3 Ports)
(Orange Cap)
Load Side (6 Ports)
(White Cap)
Single Ballast
(Red)
Switchable/Step
Dimming
Full-Light Output
Neutral
Hot #2
(Red)
BALLAST

Summary of content (2 pages)