Install Instructions

PowerPlug™ Luminaire Disconnect -
Model 102
Installation Instructions:
To be sold only with installation instructions.
WARNING: This is a current rated device. Use in applications involving amperage
beyond its rating can be dangerous and cause electrical fires. See note on this page
for allowable current and voltage levels and do not exceed those levels.
Instructions:
Conductor installation:
1. Wiring must comply with all
applicable electrical codes.
2. Turn off power before removing or
installing disconnect.
3. Strip wires to 3/8 inch (9,5 mm).
4. Grip black ballast wire firmly and push
conductor into white cap port marked
with black circle.
5. Grip white ballast wire firmly and push
conductor into same side of connector
in port marked with white circle.
6. Grip black supply wire firmly and push
conductor into port opposite black ballast wire.
7. Grip white supply wire firmly and push conductor into remaining port.
8. Use only one conductor per port and assure that no copper is exposed on any of the wires
inserted.
9. See disconnect de-mate/mate installation instructions below when replacing ballasts.
10. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT REMOVE
AND REPLACE WIRES.
DANGER
NEVER remove wires from product as contact with electricity can cause serious injury or death. Shut
off power at the circuit breaker or remove fuse when installing this product.
SAFETY NOTICE
Improperly installed electrical wiring can be dangerous and cause electrical fires. This
product must be used in accordance with the current rating and wire sizes listed. Consult local building
code before doing any electrical work.
COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105 C (221F)
maximum. Flame Rated UL94V-0.
Voltage Rating: 600 Volts Maximum Current Rating: 6 Amps Maximum
Wire Range:
Solid: 12-18 AWG
Stranded: 12-14 AWG (19 Strand or less)
Stranded Tin Bonded: 12-14 AWG (19 Strand or less)
16 AWG (26 Strand or less)
18 AWG (16 Strand or less)
Disconnect de-mate / mate installation
1. To de-mate, grasp disconnect at each end and pull apart to separate the disconnect halves.
Do NOT pull on wires.
2. To mate the disconnect, grasp each disconnect half, align halves, and push together.
3. Completed connection should appear as shown.
3/8” Strip Length
Indicator
Line Side Wires
12 - 18 AWG
Insert black ballast
wire into port marked
with a black circle
Load Side Ballast Wires
18 AWG (typ.)
IDEAL INDUSTRIES, INC.
Becker Place
Sycamore, IL 60178, U.S.A.
800-435-0705 Customer Assistance
www.idealindustries.com