User Manual
IHC-200 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
9
diP
Decimal Point
Position
0~3
1
diL
Input Lower Limit
Value
-1999~+9999
1 Digital
0
diH
Input Upper Limit
Value
-1999~+9999
1 Digital
1000
SC
Sensor Calibration
-199~+999
0
oP1
Output Mode
0/2:Time Duty
0
1:0-10mA
Opl
Output Lower Limit
0~220
1%
0
Oph
Output Upper Limit
0~220
1%
100
ALP
Alarm Function
0~31
Table 2
0
CF
System Function
2: Heater
2
3:Cooler
Addr
Address
0~63
1
Baud
Baud Rate
0~4800
9600
dl
Input Digital Filter
0~20
Filter
Effect
0
run
Run Mode
0:Manual
2
1:Automatoc
2:No Manual
LOC
Lock Function
0~999
40
EP1 ~EP8
8 User-defined
Parameters
Select any
Parameter from
this Table
Except
LOC and
EP1~EP8
none
User-defined Parameter: In the process of setting parameters, the display modes of
last eight parameters are difference from the previous. PV screen displays prompt EP1 -
EP8, SV screen displays various prompts of technical parameters Setting (e.g. HiAL, LoAL,
dHAL and so on). Press “︽”Key(or“︾”Key), The technical parameters in SV screen will
be listed in proper order as the above parameters table. After that, press “SET” key
confirm and enter next setting. “none” needs to be set if user don’t need to use the user-
defined parameter. Press “SET” key to set these 8 user-defined parameters till all to be set,
and then return to normal status.
Datalock (LOC): When the setting values of LOC are not “2”, “40” or “808”, the
instrument only allows to set 0-8 self-defined parameters and LOC parameters themselves.
User can set all parameters only when setting LOC value is “2”, “40” or “808”. Details are
as follows:
Loc=0, Temperature setting value and EP1-EP8 can be revamped.
Loc=1, Data can not be revamped, only can be checked.(Except LOC parameters)