Primary Network Devices
There are twenty-three devices that connect directly to the primary Innotech network. These are
listed in table 1 below:
Part
Number
Comms
Terminals
Comms Isolation Screen Type Description
GENIIxLD
G+ S N+G- N-
Fully isolated
So Earth to Earth
power terminal 3
Genesis Version 5
Hardware
MPCIILN
G+ S N+G- N-
Fully isolated
So Earth to Earth
power terminal 3
MPC Version 6
Hardware
GENESIS II V4
G+ S N+G- N-
Optional
Full Isolation Card
Tie Terminal
Genesis Version 4
Hardware (obsolete)
GENII MPC
G+ S N+G- N-
Fully isolated
So Earth to Earth
power terminal 3
MPC Version 4
Hardware
GENESIS II V3
N+ SN-
G+ SG-
Optional
Full Isolation Card
Tie Terminal
Genesis Version 3
Hardware (obsolete)
MAXIM 1010
G+ S N+G- N-
Robust
High protection
So Earth to power
supply 0V terminal
Maxim 1010
MAX3xLx
G+ S N+G- N-
Robust
High protection
So Earth to power
supply 0V terminal
Maxim Series 3
Hardware
MAX2Lx
G+ S N+G- N-
Robust
High protection
Tie Terminal
Maxim Series 2
Hardware
MM01
G+ S N+G- N-
Robust
High protection
So Earth to power
supply 0V terminal
Mini Maxim Controller
GENII
VIEWPORT
S1
-
S2
+
Fully isolated
So Earth to power
supply 0V terminal
Viewport Network
Display
MP01
S1
-
S2
+
Fully isolated
So Earth to Earth
power terminal 3
MiniPort Maxim
Network Display
Table 2-1:  Primary Network Digital Controllers and Devices