Manual

© Mass Electronics Pty Ltd 2007
Innotech Device Network Cabling Installation Instructions
Edition 3.0 dated 05.12.2013
Page 18
There are a number of rules that apply to the comms connection of a primary network.
Some of these are explained in detail in Chapter 1 of this manual.
Primary network rules:
The screen must be continuous
Only one point earthed on the screen
Even if a network has a number of devices with a so earth, one hard earth is still required on that
network
The Net and Global networks should have the same length cable run and path
If a repeater is installed, each side of that repeater is a separate network and each requires a
bonded earth connection on the screen
Using isolated devices, devices with isolated comms cards or using an isolated MPI does not alter
any of these rules
There are no End of Line termination (EOL) requirements on the primary network
2-1 Continuous Screen
The screen on a primary network needs to be continuous. That means it remains unbroken along its
entire length. As there is one ‘S’ terminal on a typical primary network device both the global and net
screens are to be connected to this tie terminal.
G+ S N+G- N-
Figure 2-1:  Typical Screen Connections
GLB Comms
NET Comms
When there is more than one connection point to earth the screen becomes a conductor and no longer performs
correctly. Care should be taken to ensure only one bonded earth point is ever connected on a primary network.
Refer to Chapter 2-6 for details on use of a Repeater in a primary network.
NOTE
G+ S N+G- N-
G+ S N+G- N- G+ S N+G- N-
Device Device Device
Figure 2-2:  Earth Connection