Page 39
CAT6 STP (Shielded Twisted Pairs), where each pair is individually shielded, are suited for use with multiple
RS485 communications channels such as the Innotech Primary Comms network. Shielding is required because of
increased pair to pair capacitance, which is the primary culprit for Global/Net channel cross talk.
NOTE
4-2.1 Primary Network
Any cable that meets or exceeds all the stated specifications is suitable for use.
Primary Network Minimum Requirements:
2 twisted pairs
Minimum conductor cross section AWG24 (0.205mm²)
Stranded core type is recommended (7 strands of 0.193mm)
Conductor resistance 80 Ohms / km or less
Overall Foil screened cable with a wire drain
Less than 50pf capacitance per metre between conductors
Less than 80pf capacitance per metre between conductor and screen
Impedance 100 – 120 Ohms
Sheath thickness 0.8mm 240V rated
Equivalent to the Belden Part #8102
4-2.2 Sub Networks
CAT6 FTP (Foil Screened Twisted Pair) cable is suitable for single RS485 communications channel
networks.
Any cable that meets all the stated specifications is suitable for use.
Sub System Network Minimum Requirements:
1 twisted pair
Minimum conductor cross section AWG24 (0.205mm²)
Stranded core type is recommended (7 strands of 0.193mm)
Conductor resistance 80 Ohms / km or less
Overall Foil screened cable with a wire drain
Less than 50pf capacitance per metre between conductors
Less than 80pf capacitance per metre between conductor and screen
Impedance 85 – 115 Ohms
Sheath thickness 0.3mm 240V rated