Manual

Page 45
Innotech Device Network Cabling Installation Instructions
© Mass Electronics Pty Ltd 2007
Chapter 6 – Factory Settings for RS485 EOL Termination
O - Fitted open C - Fitted Closed O/NA - Open with no adjustment available
Part Number Part Summary
EOL
REM
EOL
Subnet
EOL
Primary
Remarks
IWS01
innSIGHT Supervisor Web
Server
-- -- O/NA
ICS01
Innotech Control Station, Set
Point
-- -- O/NA
Header and
Jumper are not
fitted
ICS02
Innotech Control Station, Set
Point & Fan
-- -- O/NA
Header and
Jumper are not
fitted
IR11
Innotech Repeater, Single
Channel
C C -- 2 Jumpers
IR12
Innotech Repeater, Dual
Channel
-- -- O 4 Jumpers
GENII RMI Remote Module Interface C -- --
GENII IDI REM
Opto Isolated Digital Input
Module
O -- --
GENII DO REM Relay Output Module O -- --
GENII DI REM
Dry Contact Digital Input
Module
O -- --
GENII AO REM Analogue Output Module O -- --
GENII AI REM Analogue Input Module O -- --
GENII PI REM Pulse Input Module O -- --
GENII MP405
REM
Multipoint Remote Expansion
Module
O -- --
GENII MP414
REM
Multipoint Remote Expansion
Module
O -- --
GENII MP423
REM
Multipoint Remote Expansion
Module
O -- --
GENII MP432
REM
Multipoint Remote Expansion
Module
O -- --
GENII CS REM
Control Station Remote
Expansion Module
O -- --
GENII CSAH REM
Control Station Aer Hours
Remote Expansion Module
O -- --
GENII CSFCAH
REM
Control Station With 3 Speed
Fan Remote Expansion
Module
O -- --
GENII MZS REM
Multi Zone Station Remote
Expansion Module
O -- --
GENII MZSAH
REM
Multi Zone Station Aer Hours
Remote Expansion Module
O -- --
GENII WMI Wireless Module Interface O -- --
Table 6-1 Continued