Installation Manual User guide

Chapter 1
8 Concord Express Installation Instructions
Determine the Panel Location
Before permanently mounting the panel, determine the location using the
following guidelines:
To help reduce wire run lengths and labor, centrally locate the panel with
relation to detection devices whenever possible.
Avoid running wires parallel with electrical wiring or fixtures, such as
fluorescent lighting, to prevent wire runs from picking up electrical noise.
Mount the panel at a comfortable working height (about 45 to 55 inches from
the floor to the bottom of the panel, as shown in Figure 1 below).
Leave space to the left and right of the panel for wiring, phone jack, and
optional modules.
For installations that include wireless sensors, allow at least 10 inches above
the panel cabinet for the antenna.
Allow at least 24 inches in front of the panel for opening the panel door.
Figure 1: Determining panel location
Total System Power and Wire Length Guidelines
Note: A) Class 2, Class 3, and power-limited fire alarm circuits must be installed
using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical
Code ANSI/NFPA 70. Wire that extends beyond the cable jacket must be
separated from all other conductors by a minimum of 1/4-inch or by a
nonconductive barrier.