Installation Manual User guide

Chapter 2
38 Concord Express Installation Instructions
High Level Rpts (0101-cs phone 1, 0111-cs
phone 2)
Phones-CS Phone 1-2 (Default: CS
Phone 1=on, CS Phone 2=off)
When this setting is on, the panel reports to the
central station events that involve a high-level
security risk, including the following conditions:
Fire, Police, Auxiliary, Duress, and Freeze
alarms
No Activity
Receiver Failure (or jam)
System Tamper (40 incorrect keystrokes or
touchpad supervisory),
Entering or exiting Sensor Test mode
Note: For UL 1635 listed installations, this feature
must be set to on for the programmed phone
number.
To turn High-Level Reports off or on:
1. With the display showing HIGH LEVEL
RPTS OFF/ON (current setting), press 1
(off) or 2 (on). The display flashes the
entered setting.
2. Press # and the display shows the new
setting.
Low Level Rpts (0102-cs phone 1, 0112-cs
phone 2)
Phones-CS Phone 1-2 (Default: CS
Phone 1=on, CS Phone 2=off)
When this setting is on, the panel reports non-alarm
conditions to the central station, including the
following conditions:
Force Armed
Hardwire Zone Trouble (open or short)
Supervisory (wireless devices)
Low Battery (wireless devices)
Other non-alarm related conditions
Note: For UL 1635 listed installations, this feature
must be set to on for the programmed phone
number.
To turn Low-Level Reports off or on:
1. With the display showing LOW LEVEL
RPTS OFF/ON (current setting), press 1
(off) or 2 (on). The display flashes the
entered setting.
2. Press # and the display shows the new
setting.
Open/Close Rpts (0103-cs phone 1,
0113-cs phone 2)
Phones-CS Phone 1-2 (Default=off)
When this setting is on, the panel sends a
report when the system is armed (closed)
or disarmed (opened).
Note: To use this feature, the Opening
Reports and Closing Reports settings under
the REPORTING menu must be turned on.
To turn Opening/Closing Reports off or on:
1. With the display showing OPEN/CLOSE RPTS
OFF/ON (current setting), press 1 (off) or 2 (on).
The display flashes the entered setting.
2. Press # and the display shows the new setting.