Installation Manual User guide

Chapter 2
56 Concord Express Installation Instructions
Siren Options Menu
The SIREN OPTIONS menu lets you set up siren operation and supervision. The
following describes how to program the siren option settings that appear under
GLOBAL.
Immediate Trouble Beeps (0600)
Siren Options-Global (Default=off)
This setting determines whether the panel activates
trouble beeps immediately (on) once a wireless
device supervisory condition is detected, or only if
the condition exists at panel supervisory time (off).
Refer to TIMERSGLOBALSUPERVISORY
TIME.
Note: For UL Listed systems, this feature must be
on.
To turn Immediate Trouble Beeps off or on:
1. With the display showing IMMEDIATE
BEEPS OFF/ON (current setting), press 1
(off) or 2 (on). The display flashes the
entered setting.
2. Press # and the display shows the new
setting.
Disable Trouble Beeps (0601)
Siren Options-Global (Default=off)
This setting determines whether or not the
panel activates trouble beeps when a wireless
device supervisory condition is detected.
Note: For UL Listed systems, this feature must
be off.
To turn Disable Trouble Beeps off or on:
1. With the display showing DISABLE TR
BEEPS OFF/ON (current setting), press 1
(off) or 2 (on). The display flashes the
entered setting.
2. Press # and the display shows the new
setting.
UL 98 Options (0602)
Siren Options-Global (Default=off)
This setting determines whether or not the
panel complies with UL 98 requirements (4-
hour trouble beep restart, 4-hour backup battery
test, 2-hour supervisory time period for sensor
group 26Fire).
Note: For UL Listed systems, this feature must
be on.
To turn UL 98 Options off or on:
1. With the display showing UL 98 OPTIONS
OFF/ON (current setting), press 1 (off) or 2
(on). The display flashes the entered setting.
2. Press # and the display shows the new
setting.
The following describes how to program the settings that appear under SIREN
OPTIONSPARTITION 1.