Installation Manual User guide

Chapter 1
Concord Express Installation Instructions 3
RF TX TIMEOUT set to 24 hours
EXTENDED DELAY set to off
TWO TRIP ERROR set to off
ALARM VERIFY set to off
DISABLE TROUBLE BEEPS set to off
SYSTEM TAMPER set to on
Household Fire Warning System (UL 985)
Basic system plus:
Hardwire Smoke Detector:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, or 2400TH
learned into Sensor Group 26 Sentrol (ESL) models 429AT, 521B, or 521BXT
learned into sensor group 26
Wireless Smoke Sensor 60-506-319.5 or 60-645-95 learned into sensor
group 26
IMMEDIATE TROUBLE BEEPS set to on
UL 98 OPTIONS set to on
RECEIVER FAILURE set to on
SIREN VERIFY set to on
RF TX TIMEOUT set to 4 hours
ALARM VERIFY set to off
DISABLE TROUBLE BEEPS set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to
90 mA continuous using a 4.0 AH battery.
SIA System Requirements
Note: UL requirements take priority over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic
System on page 1, plus:
If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-
01.