TDS

Surge Protection Device - - HVAC Surge Protective Device
Voltage Configuration (Single Phase) 120 VAC, 50 Hz; 240 VAC, 50 Hz; 120 VAC, 60 Hz; 240 VAC, 60 Hz
Modes of Protection 3 (L1-N, L2-N, L1-L2)
Nominal Discharge Current 20 kA
Maximum Continuous Operating Voltage (L-G) 150
Maximum Continuous Operating Voltage (L-L) 300
Maximum Continuous Operating Voltage (L1-N/G) 150
Short Circuit Current Rating 100 kA
Voltage Protection Rating (L-L) 1200
Wiring Option Wire Leads
Voltage Protection Rating (L1-N/G) 700
Surge Protection TPMOV®
Phase Single
Control Specifications
Has Module Power Switch False
Surge Protection Type 1; 2
Surge Protection LED Indicator Green
Environmental Specifications
Operating Temperature -40 °F to 158 °F / (-40 °C to 70 °C)
Standards and Certifications
UL Certification cULus
RoHS Certification True
Other Certifications HVACR
UL Certification (Type 1) US SPD Type 1; Canada SPD Type 1
UL Certification (Type 2) US SPD Type 2
UL Standard Ansi/UL 1449 4th Edition
California Proposition 65 DEHP
Dimensions
Product Dimensions (H x W x D) 3 7/8 x 1 5/8 x 4 3/16 in
Wire Lead Length (in) 18
Wire Size Max #10 AWG, Tinned Copper
Packaging
Shipping Weight (lbs) 0.65
Shipping Weight (kg) 0.295
Unit Carton Height (in) 4.5
Unit Carton Width (in) 2
Unit Carton Length (in) 4.25
2/
8
Technical specifications and other information are subject to change without notice. Images can vary from original. © 03/25/2019