Specification

www.Intermatic.com
*C/B
GND (green)
Neutral (white)
Line (black)
Line (black)
SPD TYPE 1 AND 2 WIRING DIAGRAM
120/240 VAC SINGLE PHASE
SPD
*2 Pole 30 amp circuit breaker in Service Panel.
(Not required for SPD type 1 installations)
Surge Protection
IG2200 Series
Diagrams
Specification
The SmartGurad Series is UL Listed to ANSI/UL 1449 3rd Edition for SPD Type 1 and Type 2 locations. SmartGuard
Surge Protective Devices shall provide protection between each phase conductor, neutral and ground. The Maximum
Continuous Operating Voltage (MCOV) is a minimum of 150 volts AC. The Voltage Protection Rating (VPR) for all
SmartGuard Surge Protective Devices has a maximum rating of 800 volts Line to Neutral and 1500 volts Line to Line
when subjected to the ANSI/UL 1449 3rd Edition VPR and Nominal current testing (In). These Surge Protective Devices
employ MOV technology and provide individual component thermal protection and monitoring. Each IModule utilizes a
green LED protection status indicator and a blue LED power status indicator. When an IModule sacrices itself during a
surge event the green LED turns off to show that protection for that phase has diminished. The IG2200 Series rainproof
housing shall be constructed of either UV resistant polycarbonate or powder coated steel, and tested to UL Type 3R
standards for outdoor use. Each Type 1 or Type 3R enclosure is provided with ½” and ¾” knockouts to allow routing
of leads as needed for connection to SPD. Leads are tinned copper and shall be 10 gauge minimum and 18 inches in
length. The Base Surge Protective Device shall carry a 10-year limited product warranty and a $25,000 or $50,000
connected equipment coverage warranty for 10 years on appliances and electronics. The IModules limited warranty
period is three years (36 months) from the date of purchase (42 months from the date of manufacture).
Blue LED: Power indicator
Green LED: Status indicator
Alignment key of module
ON: Protection is being provided.
OFF: IModule is no longer providing
protection. Replace IModule as soon
as possible.
5 3/4"
5"
2 1/2"
8 1/2"
3 1/4"
1 5/8"
2 1/2"
5"
1 5/8"
3/4" 3/4"
1 5/8"
10 3/8"
SPD
UNIT
Main Breaker
Black (Line)
Black (Line)
White (Neutral)
Green (Ground)
Type 2 Installation
Plastic outdoor enclosure
Metal outdoor enclosure
Metal indoor enclosure
Flush mount kit IG2200--FMK
2-Pole, 30A