Installation Guide

IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3. CAUTION This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4. CAUTION – Installation and servicing should be performed by qualified personnel only. De-energize before
opening.
5. The ILB is for use with grounded LED luminaires listed to UL standards. Not for use in heated air outlets or
hazerdous locations.
6. The ILB requires an unswitched A.C. power source of 120 to 277 volts, 50/60 Hz.
7. The ILB and A.C. driver must be on the same branch circuit.
8. Do not mount near gas or electric heaters.
9. The ILB should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
10. The ILB will supply 10-60 VDC output at the individual rated specification for 90 minutes. See individual units
for output specifications.
11. Suitable for use in damp locations and plenum spaces.
12. Suitable for Luminaires, recessed Type IC (intended for insulation contact).
13. For use in 0° C minimum, 55° C maximum ambient temperatures.
14. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
15. Do not use this equipment for other than intended use.
16. Install in accordance with the National Electrical Code and local regulations.
17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation. See addendum for compatibility and covered luminaire requirements.
ILB-CP
‘A’ MOUNTING DESIGN
EMERGENCY LIGHTING EQUIPMENT
FOR LED
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 FAX (520) 741-2837
www.iotaengineering.com
SAVE THESE INSTRUCTIONS
Patented. See iotaengineering.com/patents for more details
EMERGENCY LED DRIVER FOR USE
WITH LED LUMINAIRES IDENTIFIED IN
THE MANUFACTURER’S INSTALLATION
INSTRUCTIONS
E473237
CLASS 2 OUTPUT

Summary of content (5 pages)