CAN-CR2xx - Manual, V2.0
Configuration
12
3.1 Configuration of the bus termination resistors
For each CAN circuit a bus termination resistor can be activated /deactivated by a
DIP switch. Always both positions should be set to ON / OFF.
CAN1 CAN2 CAN3
Default OFF (deactivated) OFF (deactivated) ON (activated)
Table 3-1 Configuration of the bus termination resistors
The bus termination resistors should be activated if the CAN-Repeater is the first
or the last device in the network. The termination resistor value of the total net-
work should be about 60 Ohm (120 Ohm at both ends of the network).
If the bus termination is not correct, transmission problems could happen.
3.2 Configuration of the baudrate
With DIP switch S301 the baudrate of the CAN network is defined. This setting is
necessary, because the internal logic has to detect dominant-lock states (domi-
nant level on CAN bus exceeds the maximum allowed duration).
S301-1
S301-2
S301-3 S301-4 Remark
ON
OFF OFF OFF
Baudrate between 5 kBd and 100 kBd
OFF
ON
OFF OFF
Baudrate between 100 kBd and 500 kBd
OFF OFF
ON
OFF
Baudrate equal or above 500 kBd
(Default)
Table 3-2 Configuration of the baudrate
All combinations not listed in the table aren’t allowed. If such a combination is
set, malfunction of the CAN-Repeater could happen.