Installation Guide

FASTENER REQUIREMENTS**
Figure 3
Roof to Wall
Figure 4
Horizontal Flashing
Figure 5
Kickout Flashing
Figure 6
Slabs, Path, Steps to Siding
Figure 7
Deck to Wall
Figure 8
Ground to Siding
Figure 10
Sheltered Areas
Figure 9
Gutter to Siding
Figure 12
Drip Edge
Figure 13
Block Penetration
Figure 14
Valley/Shingle Extension
Figure 11
Mortar/Masonry
BLIND NAILING
Nails - Wood Framing
Siding nail (0.09 in. shank x 0.221 in. HD x 2 in. long)
11ga. roofing nail (0.121 in. shank x 0.371 in. HD x 1.25 in. long)
Screws - Steel Framing
Ribbed Wafer-head or equivalent (No. 8 x 1 1/4 in. long
x 0.375 in. HD) Screws must penetrate 3 threads into metal framing.
Nails - Steel Framing
ET & F Panelfast
®
nails or equivalent (0.10 in. shank x 0.313 in. HD x 1-1/2 in. long)
Nails must penetrate minimum 1/4 in. into metal framing.
OSB minimum 7/16 in.
11ga. roofing nail (0.121 in. shank x 0.371 in. HD x 1.75 in. long)
Ribbed Wafer-head or equivalent (No. 8 x 1 5/8 in. long x 0.375 in. HD).
FACE NAILING
Nails - Wood Framing
6d (0.113 in. shank x 0.267 in. HD x 2 in. long)
Siding nail (0.09” shank x 0.221” HD x 2” long)
Screws - Steel Framing
Ribbed Bugle-head or equivalent (No. 8-18 x 1-5/8 in. long x
0.323 in. HD) Screws must penetrate 3 threads into metal framing.
Nails - Steel Framing
ET & F pin or equivalent (0.10 in. shank x 0.25 in. HD x 1-1/2 in. long)
Nails must penetrate minimum 1/4 in. into metal framing.
OSB minimum 7/16 in.
Siding nail (0.09 in. shank x 0.221 in. HD x 1-1/2 in. long)*
Blind Nailing is the preferred method of installation for HardiePlank
®
lap siding products. Face nailing should only be used where required by code for high wind areas and must not
be used in conjunction with Blind nailing (Please see JH Tech bulletin 17 for exemption when doing a repair). Pin-backed corners may be done for aesthetic purposes Only.
Finish nails are recommended for pin-backs. Headed siding nails are allowed. Place pin-backs no closer than 1in. from plank ends & 3/4in. from plank edge
into min. 3/8in. wood structural panel. Pin-backs are not a substitute for blind or face nailing.
Min. 2 in.
Min.
2 in.
6 in.
1in.
Z-Flashing
Z-Flashing
Z-Flashing
Min. 2 in.
Min. ¼ in.
Min. ¼ in.
Do not caulk
Min. ¼ in.
Min. ½ in.
Z-Flashing
Extend shingles
at least 1 in.
out from the
fascia when
gutters are
present
Z-Flashing
L-Flashing
As required
by IRC code
min 4 in. x 4 in.
Min. ¼ in.
Do not caulk
CLEARANCE AND FLASHING REQUIREMENTS
* When face nailing to OSB, planks must be no greater than 9 1/4 in. wide and fasteners must be 12 in. o.c. or less.
** Also see General Fastening Requirements; and when considering alternative fastening options refer to James Hardie's Technical Bulletin USTB 17 - Fastening Tips for HardiePlank Lap Siding.
HardiePlank
®
Lap Siding
HS11117 P2/4 04/18