Installation guide

5.CompleteSteps5, 8and9onpages8& 9to
completetheinstallationofnaturalgasmainspuds
intheircorrectlocations.
6. Savetheorifices& chokesremovedfromthe
applianceforfutureuse.Theywillbeneededif this
applianceisagainconvertedforusewithLPgas.
C. INVERT CAP IN APPLIANCE PRESSURE
REGULATOR, (See figure 12).
With the appliance installed the appliance regulator
should be located as shown in either figure 3 or figure 4
(pages 4 & 5). Identify the type of appliance regulator
and follow the instructions in the appropriate illustration.
D. RESET THE VALVES FOR NATURAL GAS
1. Light one burner, and set on low.
2. Remove the knob.
3. Remove the rubber grommets.
4. Locate the valve adjustment screw. See figure 13.
5. Insert a slender, thin-blade screwdriver into knob hole
and engage blade with slot in adjusting screw.
6. Starting from the LP position (see #5 on page 9, under
C. LOW FLAME ADJUSTMENT), turn the screw
counter clockwise until the flame stabilizes and
matches the pictured "low" setting on figure 14. Proper
adjustment will produce a stable, steady blue flame of
minimum size. The final adjustment should be checked
by turning the knob from high to low several times
without extinguishing the flame.
After Steps A, B and C have been completed, check
the appearance of each burner's flame at the Hi and Lo
settings against figure 14. If the flames appear too
large or too small, make sure all steps were completed
correctly.
ART# 9Zl5 _Z_-0
FIGURE17
JENN-AIR 30"
INPUT RATES - NATURAL GAS / LP GAS (BTU/HR)
RightFront 15,000/ 15,000 2000/ 2000
RightRear 9,200/ 9,100 1450/ 1550
LeftFront 5,000/ 4,000 650/ 850
LeftRear 10,500/ 9,100 1450/ 1550
Burner Ignition And
Auto-Reignition
This appliance is equipped for electronic auto-reignition by
means of a spark igniter located at the rear of each
burner. The burners are designed to light at any valve
rotation that admits sufficient gas flow to support a flame
and to automatically relight following a loss of flame due
to a draft or other adverse condition. This feature is
provided as a convenience and is not intended as a safety
feature.
CAUTION: Never cover control knobs or surrounding
control surface with utensils, towels, or other objects.
Never obstruct free air passage past the control knobs.
The knob openings have been sized to properly control air
entry to the interior of the appliance during operation.
This appliance has no air shutters. Primary air
adjustments are unnecessary. The burners are designed
to provide optimum aeration for all gases without air
shutters. When operating properly, burners should
produce clearly defined, even blue flames. If the flames
have yellow tips or are hazy and otherwise appear to
have insufficient air, obtain the services of a qualified
service technician. Some yellow tipping on LP gas is
normal.
Specified input rates are as shown in figures 17 and 18.
5BURNER MODEL
FIGURE18
JENN-AIR 36"
INPUT RATES - NATURAL GAS / LP GAS (BTU/HR)
RightFront
RightRear
LeftRear
LeftFront
Center
12,500/ 10,500
5,000/ 4,000
5,000/ 4,000
9,200/ 9,100
17,000/ 15,000
1450/1600
650/850
650/850
1450/1550
2000/2000
11