Install Instructions

TE-6300P Series Temperature Sensors Installation Instructions 1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
To meet plenum rating where Underwriters
Laboratories Inc.® UL 1995 rating is accepted, replace
the existing thermoplastic cover with the TE-6001-13
Metal Cover. To meet International Mechanical Code
standards, use all-metal components.
Installation
Dimensions
Table 1: TE-6300P Applications
Duct Probe Temperature Sensor
Model Description and Probe, in. (mm)
TE-6311P-1 1k ohm Thin-Film Nickel, 8 (203)
TE-6351P-1 1k ohm Thin-Film Platinum, 8 (203)
TE-6341P-1 2.2k ohm Negative Temperature
Coefficient (NTC) Thermistor, 8 (203)
TE-6361P-1
10k ohm Johnson Controls
® Type II, NTC
Thermistor, 8 (203)
Well Insertion Temperature Sensor
Model Description and Probe, in. (mm)
TE-6312P-1 Threaded 1k ohm Thin-Film Nickel,
8 (203)
TE-631AP-1 Threadless 1k ohm Thin-Film Nickel,
6 (152)
TE-6352P-1 Threaded 1k ohm Thin-Film Platinum,
8 (203)
TE-635AP-1 Threadless 1k ohm Thin-Film Platinum,
6 (152)
Note: See Figure 9 and Figure 10 for threadless
and threaded connections.
Duct Averaging Temperature Sensor
Model Description and Probe, in. (mm)
TE-6315P-1 1k ohm Nickel Wire, 8 (2.4)
TE-6316P-1 1k ohm Nickel Wire, 17 (5.2)
TE-6327P-1 1k ohm Platinum Equivalent Wire,
10 (3.0)
TE-6328P-1 1k ohm Platinum Equivalent Wire,
20 (6.1)
TE-6337P-1 100 ohm Platinum Equivalent Wire,
10 (3.0)
TE-6338P-1 100 ohm Platinum Equivalent Wire,
20 (6.1)
IMPORTANT: The TE-6300P Series Temperature
Sensor is intended to provide an input to equipment
under normal operating conditions. Where failure or
malfunction of the sensor could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the sensor.
IMPORTANT: Do not install the TE-6300P Series
Temperature Sensor probe in ambient temperatures
beyond the specified -50 to 220°F (-46 to 104°C)
temperature range. Installing the temperature
sensor probe in ambient temperatures beyond this
range may damage the unit and void the warranty.
Figure 1: Duct Probe Sensor Dimensions, in. (mm)
1/2-14 NPT Threads