Applications
VG7000 Series Bronze Control Valves are primarily
designed to regulate the flow of water and steam in
response to the demand of a controller in Heating,
Ventilating, and Air Conditioning (HVAC) systems.
Contact the local Johnson Controls® representative for
compatibility concerns before using the VG7000 Series
Bronze Control Valves Technical Specifications
table at
the end of this document.
These installation instructions conform to the relevant
and valid European Norm (EN) safety standards, as
well as the current laws and regulations of the
European Union. Qualified personnel are required for
the proper application of these installation instructions.
Qualified personnel are trained in the installation,
mounting, commissioning, operation, and servicing of
pneumatically and electrically actuated VG7000 Series
Bronze Control Valves; they include trainers and
instructors who have the following responsibilities:
ensure adherence to regional and international
ordinances and requirements
teach safety standards
enforce adequate facility safety and protective
operation
instruct first aid
Location of Valve Data
Each VG7000 Series Bronze Control Valve shipped
from the factory includes a brass tag chained to the
valve bonnet. The tag features technical data about the
valve, including:
code number of the valve
flow coefficient Cv of the valve
maximum allowable fluid temperature of the
controlled media
manufacturing date code of the valve (as
illustrated in Figure 1)
Installation
Pre-installation Details
Before installing a VG7000 Series Bronze Control
Valves, note the following:
Be sure to mount the valve in an upright position, in
a conveniently accessible location.
Protect the electric actuator from dripping water
that could enter the actuator housing and damage
the mechanism or motor.
Do not cover the actuator with insulating material.
Allow sufficient clearance to remove the actuator
(see Figure 2, Table 1, and Table 2).
Pipe the valve with the flow in the direction of the
arrow on the valve body, so that the plug seats
against the flow.
Wire all electrically actuated valve assemblies in
accordance with applicable electrical code
requirements. Input lines to the actuator must be
wired correctly for the valve to move in the proper
direction.
IMPORTANT: The VG7000 Series Bronze Control
Valves are intended to control saturated steam, hot
water, and chilled water flow under normal
equipment operating conditions. Where failure or
malfunction of the VG7000 Series Valve could lead
to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices,
such as supervisory or alarm systems or safety or
limit controls, intended to warn of or protect against
failure or malfunction of the VG7000 Series Valve.
Figure 1: Manufacturing Date Code
Manufacturing Facility
w wy y
M
Week
Year
FIG:mfgd
t
c
d
VG7000 Series Bronze Control Valves
Installation Instructions
VG7000
Part No. 14-1078-6, Rev. J
Issued November 15, 2013
Supersedes July 19, 2013

Summary of content (8 pages)