User Manual

Series 2200 Programmable DC Power Supplies Reference Manual Section 3: Remote operation
2200S-901-01 Rev. A/November 2011 3-7
Parameter types
Many power supply commands require parameters. Parameters are indicated by angle brackets,
such as <file_name>. There are several different types of parameters, as listed in the following table.
The parameter type is listed after the parameter. Some parameter types are defined specifically for
the arbitrary/ function generator command set and some are defined by SCPI.
Types of parameters
Parameter type
Description
Example
boolean
Boolean numbers or values
ON or 0
OFF or 0
discrete
A list of specific values
MIN, MAX
NR1 numeric
Integers
0, 1, 15, -1
NR2 numeric
Decimal numbers
1.2, 3.141516, -6.5
NR3 numeric
Floating point numbers
3.1415E-9, -16.1E5
NRf numeric
Flexible decimal number that may be type
NR1, NR2,or NR3
See NR1, NR2, NR3 examples in this
table
string
Alphanumeric characters (must be within
quotation marks)
"Testing 1, 2, 3"
Abbreviating commands, queries, and parameters
You can abbreviate most SCPI commands, queries, and parameters to an accepted short form. This
manual shows these commands as a combination of upper and lower case letters. The upper case
letters indicate the accepted short form of a command, as shown in the following figure. The accepted
short form and the long form are equivalent and request the same action of the instrument.
Figure 14: Example of abbreviating a command