Warranty

the center of the room places it closest to all points in the room.
Ceiling mounting is preferred in ordinary residential construction.
For mobile home installation, select locations carefully to avoid
thermal barriers that may form at the ceiling. For more details,
see MOBILE HOME INSTALLATION below.
When mounting an alarm on the ceiling, locate it at a minimum
of 4” (10cm) from the side wall (see figure 1).
When mounting the alarm on the wall, use an inside wall with
the top edge of the alarm at a minimum of 4” (10cm) and a
maximum of 12” (30.5cm) below the ceiling (see figure 1).
Put smoke alarms at both ends of a bedroom hallway or large
room if the hallway or room is more than 30 ft (9.1 m) long.
Install Smoke Alarms on sloped, peaked or cathedral ceilings at
or within 3 ft (0.9m) of the highest point (measured horizontal-
ly). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes
greater than 1 ft in 8 ft (.3m in 2.4m) horizontally shall be locat-
ed on the high side of the room.” NFPA 72 states: “A row of
alarms shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally” (see figure 3).
FIGURE 2
FIGURE 3
FIGURE 1