Warranty

Kitchens. Normal cooking may cause nuisance alarms. If a
kitchen alarm is desired, it should have an alarm silence feature
or be a photoelectric type.
Near fluorescent lights. Electronic “noise” may cause nuisance
alarms.
• Smoke alarms are not to be used with detector guards unless
the combination (alarm and guard) has been evaluated and
found suitable for that purpose.
3. INSTALLATION INSTRUCTIONS
WIRING REQUIREMENTS
This smoke alarm should be installed on a U.L. listed or recog-
nized junction box. All connections should be made by a quali-
fied electrician and must conform to article 760 of the U.S.
National Electrical Code, NFPA 72 and/or any other codes having
jurisdiction in your area.
The appropriate power source is 120 Volt AC Single Phase sup-
plied from a non-switchable circuit which is not protected by a
ground fault interrupter.
WARNING: This alarm cannot be operated from power derived
from a square wave, modified square wave or modified sine
wave inverter. These type of inverters are sometimes used to
supply power to the structure in off grid installations, such as
solar or wind derived power sources. These power sources pro-
duce high peak voltages that will damage the alarm.
WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT
BEFORE WIRING THE ALARM.
For alarms that are used as single station, DO NOT CONNECT
THE RED WIRE TO ANYTHING. Leave the red wire insulating cap
in place to make certain that the red wire cannot contact any
metal parts or the electrical box.
When alarms are interconnected, all interconnected units must
be powered from a single circuit.
A maximum of 24 Kidde/Lifesaver devices may be interconnect-
ed in a multiple station arrangement. The interconnect system
should not exceed the NFPA interconnect limit of 12 smoke
alarms and/or 18 alarms total (smoke, heat, carbon monoxide,