Specification Sheet

Worry-Free Kitchen Smoke Alarm
Sealed Lithium Battery Power with Safety Light
Model P3010K-CO
Architectural and Engineering
Specifications
The combination smoke and carbon monoxide alarm shall be
Kidde model number P3010K-CO or approved equal. It shall
be powered by a non-replaceable lithium battery with a 10-year
life. The lithium battery shall be sealed in the unit to prevent
removal and/or tampering. The unit shall incorporate a photo-
electric smoke sensor and an electrochemical carbon monoxide
sensor. The CO sensor shall be of a fuel cell design and provide
accuracy of +/- 20% + 15 PPM. The temperature operating
range shall be between 40ºF and 100ºF (4ºC and 38ºC) and the
humidity operating range shall be 10%-85% non-condensing
relative humidity.
The alarm can be installed on the surface of any wall or ceiling
following the UL/Manufacturer’s approved placement guide-
lines. The alarm shall incorporate an automatic activation fea-
ture that will activate the unit as soon as it is attached to the
mounting bracket, no other steps are involved.
The alarm shall include a test button that will electronically
simulate the presence of smoke and CO and cause the unit to
go into both modes of alarm. This sequence tests the unit’s
electronics to ensure proper operation.
The CO sensor will not alarm to levels of CO below 30 PPM and
will alarm in the following time range when exposed to the cor-
responding levels of CO.
70 PPM CO Concentration 60 – 240 Minutes
150 PPM CO Concentration 10 – 50 Minutes
400 PPM CO Concentration 4 – 15 Minutes
The alarm shall include a piezoelectric horn that is rated at 85
decibels at 10 feet. For a CO incident, the horn will sound in
the repetitive manner – four (4) fast beeps, a short pause, four
(4) fast beeps, a short pause. In a smoke incident, the horn will
sound in the repetitive manner – three (3) beeps, a pause, three
(3) beeps, a pause. The red LED will flash in conjunction with
the alarm sound.
The unit shall indicate a low battery condition with a brief alarm
chirp and LED flash once every 30 seconds. In standby condi-
tion, the LED will flash every 60 seconds for the first 10 minutes
following power on or test, and once every 10 minutes thereaf-
ter. It will also flash every 10 seconds while in Hush mode.
The smoke alarm shall include an End of Life Alert, where ten
years after initial power-up the unit shall chirp two times every
30 seconds to indicate the alarm needs to be replaced. The
End of Life indication can be silenced for 3 days at a time for
a maximum of 30 days. The unit shall have a deactivation
switch to disable it and make it safe for disposal.
The unit shall at a minimum meet the requirements of
UL217, UL 2034, NFPA 72, (chapter 11 2002 edition) The
State of California Fire Marshall, NFPA 101 (One and two
family dwellings), Federal Housing Authority (FHA), Housing
and Urban Development (HUD). It shall also include a 10-year
manufacturer’s limited warranty.
Ordering Information
Technical Specifications
Model: P3010K-CO
PowerSource: Sealed Lithium Battery
Sensor: Smoke: Photoelectric
CO: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
HumidityRange: 10%-85% non-condensing
relative humidity (RH)
Size: 5.22” in diameter x 1.6” depth
Weight: 1 lb.
Interconnects: No
Warranty: 10 year limited
1.6"5.22"
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-P3010K-CO sheet rev. 03-2013
Part No: I 2 of 5 UPC
Pack Quan-
tity
Dimensions
(w” x d” x h”) Weight
Case/
Skid
Skid
Weight
21010170 100-47871-10061-0 0-47871-10061-3 3-PK (Clam) 7.25 x 1.75 x 11 1 lbs N/A N/A
21010071 100-47871-10071-9 0-47871-10071-2 6-PK (Box) 5.75 x 2 x 6.25 1 lbs N/A N/A