G3601-8911-8
ENGLISH 3 WARNING Before the generator can be connected to a building's electrical system, a licensed electrician must install an isolation (transfer) switch in the building's main fuse box. The switch is the connection point for generator power and allows selection of generator or main line power to the building. This will prevent the generator from charging the main power line (backfeeding) when the main power supply has failed or has been turned off for line repair.
You are now the proud owner of a KUBOTA Diesel Engine Generator. This generator is a product of KUBOTA quality engineering and manufacturing. It is made of fine materials, under a rigid quality control system. And will give you long, satisfactory service. To obtain the more (productive) use of your generator, please read this manual carefully. It will help you become familiar with the operation of the generator, and contains many helpful hints about generator maintenance.
ENGLISH CONTENTS 3 SAFE OPERATION ................................................................................................................... 1 SERVICING OF GENERATOR....................................................................................................... 1 SPECIFICATIONS .......................................................................................................................... General Type (50 Hz) ........................................................................
MAINTENANCE .......................................................................................................................... SERVICE INTERVALS .............................................................................................................. DAILY CHECK ........................................................................................................................... Walk around Inspection .........................................................................................
ENGLISH CONTENTS TROUBLESHOOTING ................................................................................................................. Generator Troubleshooting ................................................................................................. When it is Difficult to Start the Engine ................................................................................ When Starter does not Start .........................................................................................
1 3 SAFE OPERATION Careful operation is your best insurance against an accident. Read and understand this operator’s manual carefully before operating the generator. All operators, no matter how much experience they may have had, should read this manual and all labels on the generator before operating the generator. It is the owner's responsibility to instruct all operators in safe operation. Be sure to observe the following for safe operation.
ENGLISH 2 SAFE OPERATION CHECK BEFORE OPERATION & STARTING THE ENGINE ¡ Always turn off the circuit breaker and all switches for the electrical devices before starting the generator. ¡ Check the wiring and connections of the electrical devices before starting the generator. ¡ Be sure to check the engine before operation. If something is wrong with the engine, repair it immediately and before operation. ¡ Keep all guards and shields in place before operating the generator.
KEEP THE AREA AROUND THE ENGINE CLEAN ¡ Be sure to stop the engine before cleaning. ¡ Keep the engine clean and free of accumulated dirt, grease and trash to avoid a fire. Store flammable fluids away from sparks and fire. ¡ DO NOT stop the engine without idling. Sudden stops can cause temperatures around the engine to rise suddenly. Keep the engine idling for about 5 minutes before stopping. SAFE HANDLING LUBRICANTS OF FUEL AND ¡ Always stop the engine before refueling and/or lubricating.
ENGLISH 4 SAFE OPERATION EXHAUST GASES & FIRE PREVENTION ¡ Engine exhaust fumes can be very harmful if allowing them to accumulate. Be sure to run the engine in a well ventilated place and where there are no people or livestock near the generator. ¡ DO NOT operate the generator in a closed area such as inside houses, warehouses, tunnels, wells, ship holds, tanks, etc. or places without proper ventilation.
ESCAPING FLUID ¡ Relieve all pressure in the oil and the cooling systems before any lines, fittings or related items are removed or disconnected. ¡ Be alert for possible pressure when disconnecting any device from a system that utilizes pressure. DO NOT check for pressure leaks with your hand. High pressure oil or fuel can cause serious personal injury. ¡ Escaping fluid under pressure has sufficient force to penetrate skin causing serious personal injury. ¡ Fluid escaping from pinholes may be invisible.
ENGLISH 6 SAFE OPERATION CAUTIONS AGAINST BURNS & BATTERY EXPLOSION ¡ To avoid burns, be alert for hot components, e.g. muffler, muffler cover, radiator, pipes, hoses, engine body, coolant, engine oil, etc. during operation and just after the engine has been shut off. ¡ DO NOT remove the radiator cap while the engine is running or immediately after stopping. Otherwise hot water from the radiator will escape under pressure causing injury by scalding.
CONDUCTING SAFETY CHECKS & MAINTENANCE ¡ Know how to stop the generator quickly, and understand operation of all the controls. DO NOT permit anyone to operate the generator without proper instruction. ¡ When checking engine or servicing, place the generator in an open area and level ground. DO NOT work on anything that is supported ONLY by lift jacks or a hoist. Always use blocks or safety stands to support the generator before servicing. ¡ Detach the battery from the generator before conducting service.
ENGLISH 8 SAFE OPERATION DANGER, WARNING AND CAUTION LABELS Pay special attention to all labels on the generator. Refer to following representations for labels used on the KJ-Series Generator. Labels are available individually from your KUBOTA Dealer. (1) Part No. G3341-8851-0 (5) Part No. G3907-8832-0 (6) Part No. G3352-8836-0 (2) Part No. G3341-8824-0 (7) Part No. G3341-8830-0 (3) Part No. 18620-8806-0 (8) Part No. G3341-8831-0 (4) Part No.
(9) Part No. G3781-8825-0 (11) Part No. G3341-8895-0 (10) Part No. G3102-8806-0 (12) Part No.
ENGLISH 10 SAFE OPERATION CARE OF DANGER, WARNING AND CAUTION LABELS 1. Keep danger, warning and caution labels clean and free from obstructing material. 2. Clean danger, warning and caution labels with soap and water, dry with a soft cloth. 3. Replace damaged or missing danger, warning and caution labels with new labels from your local KUBOTA Dealer. 4.
SERVICING OF GENERATOR Your dealer is interested in your new generator and has the desire to help you get the most value from it. After reading this manual thoroughly, you will find that you can do some of the regular maintenance yourself. However, when in need of parts or major service, be sure to see your KUBOTA dealer. For service, contact the KUBOTA Dealership from which you purchased your generator or your local KUBOTA dealer.
ENGLISH 2 SPECIFICATIONS SPECIFICATIONS 쎱 General Type (50Hz) Model Generator Generator type Type Rated output Unit kVA kW KJ-S130VX KJ-T130DX KJ-T180VX KJ-T300 PX-322KE3 PX-316KU1 PX-312KU3 PX-316KU3 Revolving field, self-excited brushless AC generator 12.5 12.5 18.0 30.0 12.5 10.0 14.4 24.0 1 Phase 4 wires 3 Phases 12 wires 100 80 Continuous 380 110/220 380 415 380 415 45.6 56.8 19.0 17.4 27.3 25.0 50 H Self-excitation 4 Direct drive 1500 No.
쎱 General Type (60Hz) Model Generator Generator type Type Rated output Unit kVA kW KJ-S150VX KJ-T160DX KJ-T210VX PX-316KU1 PX-312KU3 PX-316KU3 Revolving field, self-excited brushless AC generator 15.0 15.6 21.0 15.0 12.5 16.8 1 Phase 4 wires 3 Phases 12 wires 100 80 Continuous 110/220 120/240 220 380 220 380 68.2 62.5 40.9 23.7 55.1 31.9 60 H Self-excitation 4 Direct drive 1800 No. of phase % Power factor Rating Rated voltage V A Current Rated frequency Hz Insulation class Excitation No.
ENGLISH 4 SPECIFICATIONS 쎱 AUS Type (50Hz) Model Generator Generator type Type Rated output No. of phase Unit kVA kW KJ-S130VX-AUS KJ-T130DX-AUS KJ-T180VX-AUS KJ-S240-AUS KJ-T300-AUS PX-316KU1 PX-312KU3 PX-316KU3 PX-322KE1 PX-322KE3 Revolving field, self-excited brushless AC generator 12.5 12.5 18.0 24 30 12.5 10.0 14.4 24 1 Phase 4 1 Phase 4 3 Phases 12 3 Phases 12 wires wires wires wires 100 80 100 80 Continuous 240/415 240 240/415 240 52.1 17.4 25.0 100 41.
INSTRUMENT PANEL AND PART NAMES 쎱 Control Panel 1 Phase Type [KJ-S130VX, KJ-S150VX] 3 Phases Type [KJ-T130DX, KJ-T180VX, KJ-T300, KJ-T160DX, KJ-T210VX] [KJ-S240-AUS] [KJ-T300-AUS] (1) A.C. Voltmeter (2) Frequency meter (3) A.C. Ammeter (4) Pilot lamp (5) Glow plug lamp (6) A.C.
ENGLISH 6 INSTRUMENT PANEL AND PART NAMES 쎱 Part Names (1) Fuel tank cap (2) Cooling air inlet (3) Door (4) Cooling air outlet (5) Handling hook (6) Radiator top cover (7) Door handle (8) Stop knob (for KJ-S130VX, KJ-T130VX, KJ-T180VX) (9) Load center cover (10) Stop switch (for KJ-S240, KJ-T300) (1) Muffler (2) Alternator (3) Radiator (4) Oil dipstick (5) Engine oil drain plug (6) Fuel tank drain tap (7) Fuel tank (8) Fuel tank tap (9) Fuel filter cartridge (10) Stop lever (11) Battery (12) Oil filter
7 PREPARATION FOR FIRST OPERATION 3 CAUTION: To avoid personal injury: ¡ To avoid personal injury from contact with moving parts; ¡ Never open the door or generator side cover while the engine is running. ¡ DO NOT touch muffler or exhaust pipes while they are hot; Severe burns could result. 쎱 How to Open the Door Open the machine door and hold it open with the door rod q. ¡ Keep all sparks and flames away from the battery and fuel tank.
ENGLISH 8 PREPARATION FOR FIRST OPERATION 쎱 Engine Oil 쎱 Coolant The generator has been shipped without engine oil. Fill with oil or it will not start. 1. Place the machine on a level surface. 2. Remove the oil cap. 3. Add engine oil of grade CD or higher, up to the upper mark on the oil dipstick. (1) Engine oil cap (2) Oil dipstick Engine oil capacity liters.
PREPARATION FOR FIRST OPERATION 5. The fuel level can be checked on the fuel gauge. (1) Reserve tank (2) Cap (A) “FULL” Upper line 1.1L (B) “LOW” Fuel tank capacity liters 쎱 Fuel 3 (1) Fuel gauge WARNING: To avoid personal injury: ¡ DO NOT refuel when engine is running or hot. ¡ Always shut off the engine before refueling. ¡ DO NOT overfill fuel system. If any fuel overflows, wipe it up completely before starting operation. ¡ When refueling, keep all flames, sparks and cigarettes away from generator.
ENGLISH 10 PREPARATION FOR FIRST OPERATION 쎱 Bleeding Air from the Fuel Lines 3 CAUTION: To avoid personal injury: ¡ Always keep the air bleeding plug on the fuel filter closed except when bleeding the air. ¡ DO NOT perform bleeding operation when engine is hot. NOTE: Always bleed the air completely in the following circumstances. ¡ When adding fuel into an empty tank. ¡ When refueling after the engine stops after running completely out of fuel.
2. Capacity of Electrical Devices Possible APPLICATION RANGE You can operate the KJ-series generator in the following range. Typical Apparatus 11 AC devices Electric power (W) = Voltage (V) x Current (A) ÷ Power factor Power factors of commonly used devices are listed in the following table. Power factor Light and heaters Commutator motor KJ-S130VX 12.5 kVA (12.5 kW) 8.0 kVA (6.4 kW) KJ-S240 24.0 kVA (24.0 kW) KJ-T130DX Induction motor Single-phase induction motor 0.4 to 0.
ENGLISH 12 PRE-OPERATION CHECK PRE-OPERATION CHECK DAILY CHECK To prevent problems from occurring, it is important to know the conditions of the generator well. Always perform the following check items before starting the generator. 3 CAUTION: To avoid personal injury: ¡ Before checking or servicing the generator, make sure it is on a level surface with the engine shut off.
13 ENGLISH OPERATING THE ENGINE OPERATING THE ENGINE 3 CAUTION: To avoid personal injury: ¡ Read "Safe Operation" in the front of this manual. ¡ Read the danger, warning and caution labels located on the generator. ¡ To avoid the danger of exhaust fume poisoning, do not operate the engine in a closed building without proper ventilation. ¡ Always turn OFF the circuit breaker before starting the generator. ¡ Turn OFF all switches on the electrical devices.
ENGLISH 14 OPERATING THE ENGINE 4. Insert the key into the key switch. 5. Turn the key to the "START" position and [KJ-T130DX, KJ-T180VX, KJ-T300, KJ-T160DX, KJ-T210VX] release when the engine starts. (1) Main switch (Key) (A) “OFF” (B) “ON” (C) “GLOW” (D) “START” IMPORTANT: ¡ Do not run the starter motor continuously for more than 10 seconds at a time, or it may damage the starter. If the engine fails to start, wait for about 30 seconds and try again. 6.
2. Turn the key to the “START” position 15 ENGLISH OPERATING THE ENGINE 2. Close the fuel tank tap. and the engine should start. (If the engine fails to start after 10 seconds, turn off the key for 30 seconds. Then repeat steps (5) and (6). To protect the battery and the starter, make sure that the starter is not continuously turned for more than 10 seconds.
ENGLISH 16 OPERATING THE ENGINE 쎱 Stop Switch (AUS type) zEngine model : V3300-EBGx x 3 CAUTION: To avoid personal injury: ¡ Push the stop switch in case of emergency. The engine stops when the key’s turned off (counterclockwise). If the engine does not stop, push the stop switch. 쎱 Stop Lever (General type) 3 CAUTION: To avoid personal injury: ¡ Turn the stop lever to the left and hold it until the engine stops in case of emergency. The engine stops when the key is turned off (counterclockwise).
WARMING UP Connecting the Load (General type) Be sure to warm up the engine, not only in winter, but also in warmer seasons. An insufficiently warmed-up engine can shorten its service life. 3 Warm-up in the Low Temperature Range In cold weather, the engine oil may be cold with increased viscosity. This can delay oil circulation or abnormally low oil pressure for some time after engine start-up. This can result trouble in the lubrication circuit or damage to the engine moving parts.
ENGLISH 18 OPERATING THE ENGINE Single phase 3 terminal type ¡ For single phase Power Source: ¡) KJ-S130VX 50Hz 110V ¡) KJ-T130DX, KJ-T180VX, KJ-T300 50Hz 220,240V 50Hz 220V ™) KJ-S150VX 60Hz 110V 60Hz 220V, 240V (1) Light (2) Television (3) Air conditioner Use U-N V-N Use U-V ¤) KJ-T160DX, KJ-T210VX 60Hz 127,220V Use U-N V-N Use U-V (1) Light (2) Television (3) Air conditioner (4) Electric Drill (5) Motor Pump 3 phase and single phase 4 terminals type ¡ For 3 phase power source ¡) KJ-T130
¡ For Single Phase Power Source: ¡) KJ-T130DX, KJ-T180VX, KJ-T300 50Hz 220,380,415V single phase ¤) KJ-T160DX, KJ-T210VX 60Hz 220,380V single phase Use U-V V-W W-U Use U-V V-W W-U (1) Circuit breaker (2) Circuit breakers for sockets [KJ-S240-AUS] (1) Electric Drill (2) Motor Pump (3) Air conditioner Connecting the Load (AUS type) 3 WARNING: To avoid personal injury: ¡ Connect or disconnect the load to the AC receptacles or terminals only when the engine is stopped.
ENGLISH 20 OPERATING THE ENGINE 2. Connect the load to the A.C. sockets. KJ-S240 Use U-V ¡) KJ-S130VX-AUS 50Hz 240V (1) Light (2) Television (3) Air conditioner ™) KJ-T130DX-AUS, KJ-T180VX-AUS 50Hz 240/415V (4) Electric Drill (5) Motor Pump KJ-T300 ¡ For 3 phase power source Use U-V-W 2. Connect the load to the A.C. output terminals. (1) Motor ¡ For single phase power source: Use O-U O-V O-W (1) Terminals (output) 3. Finally be sure to close the cover and tighten up the lock screws.
21 OPERATING THE GENERATOR OPERATING PROCEDURE TO SUPPLY THE ELECTRIC POWER 1. Start the engine according to the "OPERATING THE ENGINE" 2. Warm the engine with section load. 3. Turn ON the circuit breaker. IMPORTANT: ¡ When there is a severe overload or single phase short circuit in the wiring of the three phase generator, the circuit breaker turns OFF. If this happens, eliminate the cause and turn the circuit breaker ON again.
ENGLISH 22 OPERATING THE GENERATOR OPERATING PROCEDURE TO STOP SUPPLYING THE ELECTRIC POWER 5. Turn the fuel tank tap to the “OFF” position. 1. Turn OFF all electrical device switches for connected loads. 2. Turn OFF the circuit breaker. (1) Fuel tank tap (1) Circuit breaker (A) “STOP” 3. Allow the engine to run with no load for about 5 minutes before stopping the engine completely. 4. Turn the main switch (key) to the “OFF” position.
MAINTENANCE ANTI-FREEZE & DISPOSAL OF FLUIDS ¡ DO NOT run the engine with installed safety guards detached. ¡ Anti-freeze contains poison. Wear rubber gloves to avoid personal injury. In case of contact with skin, wash it off immediately. ¡ DO NOT mix different types of Anti-freeze. The mixture can produce chemical reaction causing harm. Use approved or genuine KUBOTA Anti-freeze. ¡ Be mindful of the environment and the ecology. Before draining any fluids, find out the correct way of disposing of them.
ENGLISH 24 MAINTENANCE SERVICE INTERVALS Observe the following for service and maintenance. The lubricating oil change intervals listed in the table below are for Classes CF, CE and CD lubricating oils of API classification with a low-sulfur fuel in use. If the CF-4 or CG-4 lubricating oil is used with a high-sulfur fuel, change the lubricating oil at shorter intervals than recommended in the table below depending on the operating condition. IMPORTANT must be done after the first 50 hours of operation.
25 NOTE: Lubricating oil With the emission control now in effect, the CF-4 and CG-4 lubricating oils have been developed for use of a lowsulfur fuel for on-road vehicle engines. When an off-road vehicle engine runs on a high-sulfur fuel, it is advisable to employ the CF, CD or CE lubricating oil with a high total base number. If the CF-4 or CG-4 lubricating oil is used with a high-sulfur fuel, change the lubricating oil at shorter intervals.
ENGLISH 26 MAINTENANCE 쎱 Checking Coolant Level 3 WARNING: To avoid personal injury: ¡ DO NOT remove the radiator pressure cap or reserve tank cap while the engine is running under heavy load or immediately after it has been stopped, or hot water may gush out, scalding people nearby. Remove the radiator cap more than 10 minutes after the engine has been stopped. 1. Check to see that the coolant level is between the "FULL" and "LOW" marks of reserve tank. 2.
EVERY 100 HOURS 쎱 Cleaning Air Cleaner Element Since the air cleaner employed on this engine is a dry type, never apply oil to it. 1. Open the evacuator valve once a week under ordinary conditions - or daily when used in severe or dusty conditions. This will get rid of large particles of dust and dirt. 2. Wipe the inside air cleaner clean with cloth if it is dirty or wet. 3. Avoid touching the element except when cleaning. 4.
ENGLISH 28 MAINTENANCE Evacuator Valve Open the evacuator valve once a week under ordinary conditions - or daily when used in dusty condition - to get rid of large particles of dust and dirt. IMPORTANT: ¡ If the dust cup is mounted incorrectly, dust or dirt will not collect in the cup and allow the dust to come into direct contact with the element and thus require the element be replaced prematurely.
Fuel Line Air Bleeding 1. Fill the fuel tank with fuel. 2. Open the fuel tank tap. 3. Turn the plug counterclockwise on the filter two or three times. 4. If there is no air in the fuel, tighten the plug. 5. Wipe up spilled fuel immediately. (See “Bleeding Air from the Fuel Lines” in PREPARATION FOR FIRST OPERATION.) Checking Battery Electrolyte 3 DANGER: To avoid the possibility of battery explosion: The battery comes in two types: refillable and non-refillable.
ENGLISH 30 MAINTENANCE Engine oil capacity L Model Capacity KJ-T130DX, KJ-T160DX zEngine model : D1703x KJ-S130VX, KJ-S150VX, KJ-T180VX, KJ-T210VX zEngine model : V2203x KJ-S240, KJ-T300 zEngine model : V3300x 5.6 7.6 13.2 IMPORTANT: ¡ Engine oil should be MIL-L-2104C or have properties of API classification CD grades or higher. Change the type of engine oil according to the ambient temperature.
EVERY 500 HOURS Replacing Oil Filter Cartridge 1. Replace the oil filter cartridge every 500 hours of use. (Every second oil change.) 2. Coat the new filter gasket lightly with clean oil. 3. Tighten it securely by hand. 4. When the filter is replaced, the engine oil level will drop. Run the engine for a few minutes, and check for oil leaks. Re-check the oil level. If the oil level is too low, add engine oil up to the specified level.
ENGLISH 32 MAINTENANCE 쎱 Cleaning the Water Separator (Sedimenter) zEngine model : V3300-EBGx x ¡ Every 250 hours of operation, clean the fuel filter in a clean place to prevent dust contamination. ¡ When the marker comes close to the drain out level, remove the screw ring and let water flow out of the filter bowl. 1. Turn the fuel lever to the “CLOSE” position. EVERY 1000 HOURS 쎱 Replacing Air Cleaner Element (See “Cleaning Air Cleaner Element” in every 100 hours maintenance.
BATTERY 3 WARNING To avoid personal injury. ¡ Be careful not to let the battery electrolyte contact your body or clothing. ¡ Wear eye protection and rubber gloves, since the diluted sulfuric acid solution burns skin and eyes, and eats holes in clothing. Should this occur, immediately wash it off with running water and get medical attention. 33 ¡ When disconnecting the cable from the battery, start with the negative terminal, and when connecting them, start with the positive terminal first.
MAINTENANCE ENGLISH 34 When battery boost starting engine, follow the instructions below to safely start the engine. 1. Bring helper battery of the same voltage as disabled generator within easy cable reach. 2. Put on safety goggles and rubber gloves. 3. Ensure the vent caps are securely in place. (if equipped) 4. Cover vent caps with damp rags. Do not allow the rag to touch the battery terminals. 5. Attach the red clamp to the positive (red, 2 or pos.
35 ENGLISH TRANSPORTING/STORAGE TRANSPORTING/STORAGE 쎱 Transporting 3 CAUTION: To avoid personal injury: ¡When transporting the generator, remove the negative 1 battery cable, close the fuel tank tap, and keep the generator level to prevent from fuel spillage. 쎱 Checking Before Storage 3 CAUTION: To avoid personal injury: ¡ DO NOT cover the engine with a cover until it is cool to touch.
ENGLISH 36 TROUBLESHOOTING TROUBLESHOOTING 3 CAUTION: To avoid personal injury: ¡ Always perform all checks with engine stopped and cool to the touch except for those checks in which operation is required. ¡ DO NOT touch the charging section during operation. ¡ Avoid any contact with rotating fan during operation. If the engine does not function properly, use the following chart to identify and correct the cause.
쎱 When it is Difficult to Start the Engine Cause Fuel is thick and doesn't flow. Countermeasures *Check the fuel tank and fuel filter. Remove water, dirt and other impurities. *As all fuel will be filtered by the filter, if there should be water or other foreign matters on the filter, clean the filter with kerosene or replace the filter. *If air is in the fuel filter or injection lines, the fuel pump will not work properly.
ENGLISH 38 TROUBLESHOOTING 쎱 When Output is Insufficient Cause Carbon stuck around orifice of nozzle piece Countermeasures *Clean orifice and needle valve, being very careful not to damage the nozzle orifice. *Check nozzle to see if good. If not, replace with new parts. *Bad valve and excessive wear of rings, pistons and liners cause insufficient compression. Replace with new parts. *Grind valves. Fuel is insufficient. *Check fuel system. *Check lubricating oil system.
쎱 When Engine Immediately must be Stopped 쎱 When Engine Overheats 39 ENGLISH TROUBLESHOOTING
ENGLISH 40 TROUBLESHOOTING
Engine Circuit Diagram for D1703, V2203 41 ENGLISH WIRING DIAGRAM
ENGLISH 42 WIRING DIAGRAM Engine Circuit Diagram for V3300
Generator Circuit Diagram KJ-S130VX (220/110V) 50Hz, KJ-S150VX (240/120V) 60Hz, KJ-S150VX (220/110V) 60Hz 43 ENGLISH WIRING DIAGRAM
ENGLISH 44 WIRING DIAGRAM Generator Circuit Diagram KJ-T130DX (380/220V) 50Hz, KJ-T160DX (380/220V) 60Hz KJ-T180VX (380/220V) 50Hz, KJ-T210VX (380/220V) 60Hz, KJ-T300 (380/220V) 50Hz
Generator Circuit Diagram KJ-T160DX (220/127V) 60Hz, KJ-T210VX (220/127V) 60Hz 45 ENGLISH WIRING DIAGRAM
ENGLISH 46 WIRING DIAGRAM Generator Circuit Diagram KJ-T130DX (415/240V) 50Hz, KJ-T180VX (415/240V) 50Hz
Generator Circuit Diagram KJ-S130VX-AUS (240V) 50Hz 47 ENGLISH WIRING DIAGRAM
ENGLISH 48 WIRING DIAGRAM Generator Circuit Diagram KJ-T130DX-AUS (415/240V) 50Hz, KJ-T180VX-AUS (415/240V) 50Hz
Generator Circuit Diagram KJ-S240-AUS (240V) 50Hz 49 ENGLISH WIRING DIAGRAM
ENGLISH 50 WIRING DIAGRAM Generator Circuit Diagram KJ-T300-AUS (415/240V) 50Hz
51 OPERATION AND INSPECTION OF THE EMERGENCY RELAY This is an automatic engine stopping device in case of abnormal oil pressure or water temperature. This device senses any abnormal oil pressure or water temperature occurring during engine operation, and activates the stop solenoid to cut off fuel to the fuel injection pump and stop the engine. This relay has two independent timer functions, a start relay and a stop relay.