11.2 TWO-WIRE START/STOP CONTROL
NOTES:
1. Close TB-1 to TB-11 to RUN and open to STOP. TB-1 functions as a RUN input for
two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits. Refer to
Section 11.3.
2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (06). Close
TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.
3. For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE (Parameter
05) to 0-10 VDC (03) or 4-20 mA (04).