15.0 DESCRIPTION OF PARAMETERS
P01 LINE VOLTAGE SELECTION
This calibrates the drive for the actual applied input voltage. Set this parameter to HIGH (01) for 120,
220-240, and 460-480 Vac input, or LOW (02) for 200-208 and 380-415 Vac input.
NOTE: If this parameter is changed while the drive is running, the new value will not take effect
until the drive is stopped.
P02 CARRIER FREQUENCY
This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less
audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.
PARAMETER CARRIER AMBIENT OR OUTPUT
SETTING FREQUENCY DERATE (NOTE 2)
01 4 kHz 40 C or 100 %
02 6 kHz 40 C or 100 %
03 8 kHz 40 C or 100 %
04 10 kHz 35 C or 92 %
NOTES:
1. The SM Series
drive is fully rated up to 8 kHz carrier frequency. If the 10 kHz carrier
frequency is selected, the drives ambient temperature rating OR output current rating must
be derated to the value shown in the table above.
2. If this parameter is changed while the drive is running, the change will not take effect until
the drive is stopped.
P03 START METHOD
Automatic starting of equipment may cause damage to equipment and / or injury
to personnel! Automatic start should only be used on equipment that is
inaccessible to personnel.
01 NORMAL: The drive will start when the appropriate contact is closed on the terminal strip. See
Section 11 for possible control configurations.
02 START ON POWER UP: The drive will automatically start upon application of input power.