GUIDE SPECIFICATIONS
Project Name Project No. Date
Project Location 16140-11 Wiring Devices
face, body, and test/reset buttons; thermoplastic tamper-resistant shutter;
terminals accept #14 - #10 AWG solid or stranded copper or copper-clad
conductors; SafeLock
®
Protection performs an automatic test every three
seconds to insure that ground fault protection is active; auto-ground clip; indicator
light; [light almond] [ivory] [white] [brown] [black] [gray] [red] color. RoHS
Compliant.
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and
from description.
20A Hospital Grade Self-Test GFCI Tamper-Resistant Duplex Receptacles: Part
No. 2097HGTR[LA][I][W][--][BK][GRY][RED]; rated 20 amps, 125 volts; nylon
face, body, and test/reset buttons; thermoplastic tamper-resistant shutter;
terminals accept #14 - #10 AWG solid or stranded copper or copper-clad
conductors; SafeLock
®
Protection performs an automatic test every three
seconds to insure that ground fault protection is active; auto-ground clip; indicator
light; [light almond] [ivory] [white] [brown] [black] [gray] [red] color. RoHS
Compliant.
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and
from description.
15A Hospital Grade Self-Test GFCI Duplex Receptacles: Part No.
1597HG[LA][I][W][BK][GRY][RED]; rated 15 amps, 125 volts; nylon face, body,
and test/reset buttons; terminals accept #14 - #10 AWG solid or stranded copper
or copper-clad conductors; SafeLock
®
Protection performs an automatic test
every three seconds to insure that ground fault protection is active; auto-ground
clip; indicator light; [light almond] [ivory] [white] [black] [gray] [red] color. RoHS
Compliant.
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and
from description.
20A Hospital Grade Self-Test GFCI Duplex Receptacles: Part No.
2097HG[LA][I][W][--][BK][GRY][RED]; rated 20 amps, 125 volts; nylon face, body,
and test/reset buttons; terminals accept #14 - #10 AWG solid or stranded copper
or copper-clad conductors; SafeLock
®
Protection performs an automatic test
every three seconds to insure that ground fault protection is active; auto-ground
clip; indicator light; [light almond] [ivory] [white] [brown] [black] [gray] [red] color.
RoHS Compliant.
15A Hospital Grade Self-Test GFCI Isolated Ground Tamper-Resistant Duplex
Receptacles: Part No. 1597IGHGTRO; rated 15 amps, 125 volts; nylon face,
body, and test/reset buttons; thermoplastic tamper-resistant shutter; terminals
accept #14 - #10 AWG solid or stranded copper or copper-clad conductors;
SafeLock
®
Protection performs an automatic test every three seconds to insure
that ground fault protection is active; auto-ground clip; indicator light; orange
color. RoHS Compliant.
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and
from description.
20A Hospital Grade Self-Test GFCI Isolated Ground Tamper-Resistant Duplex
Receptacles: Part No. 2097IGHGTR[LA][I][W][GRY][RED][O]; rated 20 amps,
125 volts; nylon face, body, and test/reset buttons; thermoplastic tamper-
resistant shutter; terminals accept #14 - #10 AWG solid or stranded copper or