User guide

- 2 -- 1 -
LED DOWNLIGHT
Installation Manual
• Please read the 「Safety Precautions」 prior to install for your safety.
• This manual is intended to prevent product damage and protect the user’s safety.
•Violation of warnings may lead to serious injury or death.
• Violation of precautions may lead to light injury or product damage.
•Do not wipe the surface with inflammables, such as alcohol, benzene, and acetone.
•Do not use the device in places with corrosive gases.
•The color and the brightness of the lamp may differ even among the same model because the LED light source has "light dispersion".
Safety Precautions
warning
Turn power off before contact
of the product.
•Risk of electric shock.
Install a circuit breaker.
•Risk of fire and electric shock.
Use with proper rated voltage.
(less than ±10%)
•Risk of fire and product dam-
age.
1(875$/
/,9(
Wire connectors
Product’s power cables
Interior wiring of the building
1(871(8755$$//
3(
/,9/,9((
1(875$/
/,9(
Wire connectorsWire connectorsWire connectors
1(875$/
/,9(
Wire connectors
1(875$/
/,9(
Wire connectors
1(875$/
/,9(
Wire connectors
1(875$/
/,9(
Wire connectors
{c@}
If there is a ground wire, per-
form grounding work.
•Risk of electric shock.
Electric work must be per-
formed by a certified technician
according to the installation
manual.
•Inadequate power capacity and
faulty electric work may lead to
fire or electric shock.
Do not randomly connect the
power polarities.
•Risk of product damage and
accidents.
Tec hn o
l
ogy
standard
about electric
f
ac
i
litie
s
Do not install in areas that have
risks of flooding.
•Risk of electric shock and fire.
Do not use the product if impu-
rities are present in the product
or if the product is submerged.
•Risk of accidents such as elec-
tric shock and product damage.
Do not store in a humid area.
•Risk of product malfunctioning.
If the lamp turns off by itself, do
not disassemble the product.
Contact your local LGE sales
representative for repair.
•Risk of electric shock and prod-
uct malfunctioning.
Do not stare directly at the lamp
when turned on.
•Strong light may cause visual
impairment.
Do not expose the product to
water when cleaning it.
•Risk of fire and electric shock.
Do not use if the product has
been dropped or exposed to
shock.
•Risk of product malfunctioning.
Be careful not to apply exces-
sive force to the power cable.
•Otherwise, it may cause the de-
vice to drop or result in electric
shock.
Keep some distance between
the lamp and the object to be il-
luminated.
If the illumination distance is too
close or if the illumination is on a
material's surface, this may
cause discoloration or deforma-
tion of the object or cause fire.
Do not cover the device with
clothes or paper. Do not place it
near inflammables.
•Otherwise, it may cause mal-
function of the device or fire.
Do not disassemble or arbitrarily
remodel the product. Do not
use for underwater lighting pur-
poses. (Underwater landscape,
searchlight, fishing, events, etc.)
•Risk of fire and electric shocks.
Must fix the product properly on
the ceiling.
•Risk of product dropping and
causing injury to the user.
caution
MFL67404601
Installation
Dimming Terminal Connection
1
Drill and prepare the ceiling so that it can
accommodate the product.
※ Refer to page 3 for product size.
2
Connect the 3 product cables to the interior
wiring of the building. For wire connectors,
use standardized products.
※ The 4 Inch product is used for Single-
phase two-wire system. (Without P.E.)
3
Tuck up a spring of the product and then
hang it on the ceiling.
4
Insert the power cable in such a way that the
power cable does not get tangled between
the ceiling surface and the product.
5
Sufficiently lift the product so that the spring
can be inserted on the other side.
1(875$/
/,9(
Wire connectors
1(875$/
/,9(
Wire connectors
6
Check to see if the product’s exterior sur-
face is installed on the ceiling so that there
is no gap between them.
7
Turn the power switch on to verify that the
product is working properly.
※ When this luminaire is connected to branch
circuit, installation engineer must use the
connector that meets the glow-wire test of
650°C (in case of France, 850°C) or higher.
During the use of connector socket, if the power lineis
forced in, it may not be lighted due to defect contact.
-Connector Socket-
To dim the lamps, a compatible dimmer should be used.
The use of incompatible dimmers will result in damage to the products.
Before installing dimmers, verify the compatible dimmer list with your local LGE sales representative.
※ Wire dimming function is included. (0-10V)
※ Please use wire with designated thickness. (24-20AWG)
※ Be careful of the polarity for correct dimming control.
※ Maximum number of products to be connected to 1 dimming controller: 14
(Compatible dimmer: 5743 09(Legrand))
Pin No. Output Name
1 GND
2 0~10V
1
2
Make sure to turn off the main power switch off the installation space before connection.
Connect so that the colors of the 3 power cables match.
(LIVE: BROWN, NEUTRAL: BLUE, P.E.: GREEN/YELLOW)
power

Summary of content (2 pages)